New Boiler - Weather Compensator?
Discussion
Yes sludge is the worst thing you can have in a new boiler is the root of most of the problems. Viessmann are a nightmare I just cover service and repair don't do too much installation and get to work on every type of boiler out there. IMO Viessmann are nothing but trouble, god only knows how they came 3rd behind Vaillant and Worcester I'm genuinely surprised at that. I know they are not cheap but would never spend that when a worcester or valiant can be had for not much more. I always fit/recommend Vaillant for family and friends they have pretty much got it sorted with the new ecotec and have ironed out any problems they used to get over the last 8 or so years on the new ones.
To be honest, i have also been looking into the Vaillant, but it appears that even their basic OV HO boiler will not allow easy control of existing valves room stats etc, unless i purchase another load of their connection/control boxes, and even then, i would have to use their own room stats as they are all ebus.
I have also been thinking of maybe a 4 pipe system boiler and do away with the external pump.
I am a bit limited with pipe layout, boiler location as its in a kitchen cupboard, (and funds), and so i am trying to make this as easy as possible.
Whichever way i go, i would really like to introduce the WC if possible.
I have also been thinking of maybe a 4 pipe system boiler and do away with the external pump.
I am a bit limited with pipe layout, boiler location as its in a kitchen cupboard, (and funds), and so i am trying to make this as easy as possible.
Whichever way i go, i would really like to introduce the WC if possible.
Alucidnation said:
To be honest, i have also been looking into the Vaillant, but it appears that even their basic OV HO boiler will not allow easy control of existing valves room stats etc, unless i purchase another load of their connection/control boxes, and even then, i would have to use their own room stats as they are all ebus.
I have also been thinking of maybe a 4 pipe system boiler and do away with the external pump.
I am a bit limited with pipe layout, boiler location as its in a kitchen cupboard, (and funds), and so i am trying to make this as easy as possible.
Whichever way i go, i would really like to introduce the WC if possible.
Look at the baxi avanta range.I have also been thinking of maybe a 4 pipe system boiler and do away with the external pump.
I am a bit limited with pipe layout, boiler location as its in a kitchen cupboard, (and funds), and so i am trying to make this as easy as possible.
Whichever way i go, i would really like to introduce the WC if possible.
Alucidnation said:
To be honest, i have also been looking into the Vaillant, but it appears that even their basic OV HO boiler will not allow easy control of existing valves room stats etc, unless i purchase another load of their connection/control boxes, and even then, i would have to use their own room stats as they are all ebus.
I have also been thinking of maybe a 4 pipe system boiler and do away with the external pump.
I am a bit limited with pipe layout, boiler location as its in a kitchen cupboard, (and funds), and so i am trying to make this as easy as possible.
Whichever way i go, i would really like to introduce the WC if possible.
We did a straight swap in on an open vent EcoTEC plus, on a Y plan.I have also been thinking of maybe a 4 pipe system boiler and do away with the external pump.
I am a bit limited with pipe layout, boiler location as its in a kitchen cupboard, (and funds), and so i am trying to make this as easy as possible.
Whichever way i go, i would really like to introduce the WC if possible.
We did have a new room stat and a new programmer, but not the Vaillant stuff.
The only thing that was needed was a pump overrun wire.
Of course we had the system cleaned out really well, and Magnaflush pllus the MagnaClean.
It's nearly a year now and first service coming up, keeping a track of consumption as we have changed gas supplier and gas consumption has been reduced by at least 30%, in reality more, but I've sort of made a rough adjustment for a milder winter.
Interesting you say that as I have a 3 zone system installed with a nest down stairs and up.
From trying to understand the Vaillant manual, the controls are ebus with no provision for 230v switching with a wc installed.
It's possible I have gone cross eyed and missed something as I have been studying this all weekend!
From trying to understand the Vaillant manual, the controls are ebus with no provision for 230v switching with a wc installed.
It's possible I have gone cross eyed and missed something as I have been studying this all weekend!
Moles is correct you dont need to use the ebus controls the Vaillants they will all wire with everyday controls nothing fancy needed.
The ebus is a nice touch if your using a vaillant cylinder as you can alter the HW on the boiler dial but as Moles said the vaillant controls are over kill
ss
With the Viessman, from what i understand, the heating runs 24/7 and adjusts the flow temp to the rads, through heat loss and depending on outside temp. i.e. if it gets cold outside it ups the flow temp to the rads. If there is a call for DHW, the heating shuts off and the boiler ramps up the temp to heat the water, a bit like a combi. The heating curve can also be adjusted manually via the temp dial on the boiler.
With the other systems, its appears that the WC works along side internal controls, and adjusts the flow temp according to the outside temp. However, i think this stays the same, even when demand for hot water, which means it would take forever for the water to heat up.
This is all from what i can make out from the brochures and manuals, which to be honest, are not very good from any of the manufacturers.
With the other systems, its appears that the WC works along side internal controls, and adjusts the flow temp according to the outside temp. However, i think this stays the same, even when demand for hot water, which means it would take forever for the water to heat up.
This is all from what i can make out from the brochures and manuals, which to be honest, are not very good from any of the manufacturers.
Edited by Alucidnation on Monday 26th May 22:51
With the Viessman, from what i understand, the heating runs 24/7 and adjusts the flow temp to the rads, through heat loss and depending on outside temp. i.e. if it gets cold outside it ups the flow temp to the rads. If there is a call for DHW, the heating shuts off and the boiler ramps up the temp to heat the water, a bit like a combi. The heating curve can also be adjusted manually via the temp dial on the boiler.
With the other systems, its appears that the WC works along side internal controls, and adjusts the flow temp according to the outside temp. However, i think this stays the same, even when demand for hot water, which means it would take forever for the water to heat up.
This is all from what i can make out from the brochures and manuals, which to be honest, are not very good from any of the manufacturers.
With the other systems, its appears that the WC works along side internal controls, and adjusts the flow temp according to the outside temp. However, i think this stays the same, even when demand for hot water, which means it would take forever for the water to heat up.
This is all from what i can make out from the brochures and manuals, which to be honest, are not very good from any of the manufacturers.
Edited by Alucidnation on Monday 26th May 23:01
But when you're cold you want the house up to temp quick and if it's mild the heating might come on but will reach temp quicker so will turn off on the normal room stat so really all it's doing is varying its output to match the outside conditions. On a vaillant you can set its kW output by pressing 2 buttons and setting it to the output you need for your house admittedly it stays there unless you adjust it but you shouldn't really ever need to. On mine I set the output of my boiler to 10kw and leave it at 52c on dial room stat on 20 and leave the hive on all day and drop it back to 18c on a night, it comes on when it needs to and a weather compensator won't change that, each house/boiler has a certain input/output and once set up shouldn't need changing I just don't see the point in them?.
Condensing boilers are most efficient when at lower temps, 10kw is the lowest I can fix the output to but it only works if you leave the heating on all/most of the day as would take forever to warm up from scratch on a cold day, have a look in the manual a table in the back go to D0 and press i will tell you what output your ch is set to, is just a way of range rating it for different house sizes
There seems to be a contradiction here. Having the output T set low to maximise the condensing efficiency and having the boiler running when it shouldn't be, i.e. when heat isn't required.
If you have the output set low then I suppose the house will take longer to heat up therefore you will set the timer to come on earlier which will use more fuel than setting a higher boiler T and heating the house quicker. Does a higher boiler temperature in fact compromise the condensing efficiency?
Clearly the boiler should be off as much as possible. I don't understand this talk of running it 24/7, it doesn't make sense, nor does setting it back to 18 overnight. When we're asleep at night and when we're out for long periods the heating should be off or, if there's a risk of freezing, set back to say 5.
If you have the output set low then I suppose the house will take longer to heat up therefore you will set the timer to come on earlier which will use more fuel than setting a higher boiler T and heating the house quicker. Does a higher boiler temperature in fact compromise the condensing efficiency?
Clearly the boiler should be off as much as possible. I don't understand this talk of running it 24/7, it doesn't make sense, nor does setting it back to 18 overnight. When we're asleep at night and when we're out for long periods the heating should be off or, if there's a risk of freezing, set back to say 5.
I agree, however, i think the idea is that the house doesn't cool down at all with it on 24/7 as the system maintains a set temp, rather than being off for long periods, and then having to work harder to get back up to temp when required.
The WC sees the temp changes before the inside of the house does, so alters the boiler output accordingly so that the occupants don't feel the change.
Its a bit like climate in a car i guess.
Disclaimer: This is all a guess on my basic understanding and will be calling the manufacturers for specific details today.
The WC sees the temp changes before the inside of the house does, so alters the boiler output accordingly so that the occupants don't feel the change.
Its a bit like climate in a car i guess.
Disclaimer: This is all a guess on my basic understanding and will be calling the manufacturers for specific details today.
Gassing Station | Homes, Gardens and DIY | Top of Page | What's New | My Stuff