Moving a double power socket
Moving a double power socket
Author
Discussion

Sir Bagalot

Original Poster:

6,874 posts

203 months

Thursday 12th February
quotequote all
I need to move a double power socket

If it meant shortening the cable it would be easy, but I need to lengthen it, the socket is moving directly down the wall by about 3 feet.

What's the best method to lengthen the power cable down to the new location for the socket? The wall is plasterboard affixed to blockwork using dot and dab


megaphone

11,459 posts

273 months

Friday 13th February
quotequote all
Why do you need to move it? Can you just add another socket?

You've checked which way the existing cables are running?

If you're lucky you'll be able to fish new cables down behind the plasterboard, depends is there is any adhesive in the way. If not you'll need to chase out the PB.

Can you leave the old back box in place and just fit a blank plate over?

Or you can remove the back box and push the joint in the hole, then push a piece of PB in the hole and finish off.

Use Wago connectors to extend the cables. Make sure you are competent and understand what you are doing, if not get someone in who is.

Edited by megaphone on Friday 13th February 07:53


Edited by megaphone on Friday 13th February 08:06

Belle427

11,226 posts

255 months

Friday 13th February
quotequote all
I think these days its seen as ok to put a junction box in an inaccessible location if its all maintenance free.
Still not something I would do personally, I would lift the floorboards upstairs and try and run some new cables, if you have to use junction boxes then make sure you make them accessible in the future by leaving a small hatch in case of any issues.

Mr Pointy

12,767 posts

181 months

Friday 13th February
quotequote all
Have a look at Quickwire - very easy to use & might be slim enough to hide depending on how thick the void behing the pasterboard is:

https://www.quickwire.co.uk/product/2-way-splitter...

Liamjrhodes

368 posts

163 months

Friday 13th February
quotequote all
I would use WAGOs and a junction box

blueg33

44,535 posts

246 months

Friday 13th February
quotequote all
Mr Pointy said:
Have a look at Quickwire - very easy to use & might be slim enough to hide depending on how thick the void behing the pasterboard is:

https://www.quickwire.co.uk/product/2-way-splitter...
Better than Wagos in a junction box IMO.

megaphone

11,459 posts

273 months

Friday 13th February
quotequote all
blueg33 said:
Mr Pointy said:
Have a look at Quickwire - very easy to use & might be slim enough to hide depending on how thick the void behing the pasterboard is:

https://www.quickwire.co.uk/product/2-way-splitter...
Better than Wagos in a junction box IMO.
Yes agreed, these are good, as long as there is enough space.

Sir Bagalot

Original Poster:

6,874 posts

203 months

Friday 13th February
quotequote all
Is 24A ok for a double power socket?

Simpo Two

91,063 posts

287 months

Friday 13th February
quotequote all
Sir Bagalot said:
Is 24A ok for a double power socket?
On a 13A circuit?

Actual

1,558 posts

128 months

Friday 13th February
quotequote all
Simpo Two said:
Sir Bagalot said:
Is 24A ok for a double power socket?
On a 13A circuit?
The exact details would depend on the actual configuration of the circuit. If the circuit is a ring final circuit using 2.5mm2 twin and earth then it would commonly but not always have a 32A breaker at the consumer unit and each leg of ring would be rated at 16A/20A. For extending the ring final a 24A Quickwire Splitter is used on one leg of the ring and if required a second 24A Quickwire Splitter is used on the the other leg of the ring.

megaphone

11,459 posts

273 months

Friday 13th February
quotequote all
What is the socket going to be used for?

Chumley.mouse

887 posts

59 months

Friday 13th February
quotequote all
megaphone said:
What is the socket going to be used for?
Charging his phone .

Mr Pointy

12,767 posts

181 months

Friday 13th February
quotequote all
Sir Bagalot said:
Is 24A ok for a double power socket?
Yes - the rating of the 2.5mm T&E is only 23-27A depending on the method of fixing. Of course you fit two Quickwires, one in each leg of the ring.

Sir Bagalot

Original Poster:

6,874 posts

203 months

Sunday 15th February
quotequote all
In the end I employed a professional who was also kind enough to explain things as they went along

Chilly for June

366 posts

97 months

Monday 16th February
quotequote all
With a vested interest what were the steps?