quotequote all
One of my radiators wont heat up and I cant figure out why.

I've got 5 rads in all, 1 is red hot, cant hold your hand on it for more than a few seconds, it might not be relavent but this is the closest to the boiler.

2 others are hot but not too hot. One is off (had to put the fridge next to it) and the other isn't warm at all. In fact, I dont think there has been any heat in it for a few weeks now.

I've bleed all the rads. Checked it for leaks, checked the pressure in the system. All ok.

I cant figure out why the rads are different temps or why I've got a cold one.

Any help appreciated

Cheers
Stuart.

paoloh

8,617 posts

233 months

Thursday 4th December 2008
quotequote all
Power flush maybe?

MrV

2,748 posts

257 months

Thursday 4th December 2008
quotequote all
Have you tried turning all the rads off except the cold one yet?

Iain328

15,009 posts

235 months

Thursday 4th December 2008
quotequote all
tvradict said:
One of my radiators wont heat up and I cant figure out why.

I've got 5 rads in all, 1 is red hot, cant hold your hand on it for more than a few seconds, it might not be relavent but this is the closest to the boiler.

2 others are hot but not too hot. One is off (had to put the fridge next to it) and the other isn't warm at all. In fact, I dont think there has been any heat in it for a few weeks now.

I've bleed all the rads. Checked it for leaks, checked the pressure in the system. All ok.

I cant figure out why the rads are different temps or why I've got a cold one.

Any help appreciated

Cheers
Stuart.
Either there is a blockage/airlock or the system needs balancing. There's probably some instructions on the web somewhere as to the proceess to do that but briefly you need to valve down the radiators that get very hot very quickly so that some of the flow is diverted to the other rads. Essentally the water/flow will always follow the path of least resistance so you need to increase the resistance in the path to some radiators so that water flows to the others as well.

One thing you could try is to close down all the rads barring the one that is cold. If it stays cold then chances are the system is blocked somewhere. If it gets hot then you know you need to balance the thing.

dirkgently

2,160 posts

260 months

Thursday 4th December 2008
quotequote all
paoloh said:
Power flush maybe?
You work for British gas aicmfp

Impulse 9

565 posts

234 months

Thursday 4th December 2008
quotequote all
dirkgently said:
paoloh said:
Power flush maybe?
You work for British gas aicmfp
You use terrible forum banter aicmfpetihtbjwwuefotmlaahotff*


*and i claim my five pounds even though i hate the bandwagon jumping wkers who use every flavor of the month lame attempt at humor on this fking forum

singlecoil

35,831 posts

275 months

Thursday 4th December 2008
quotequote all
Impulse 9 said:
dirkgently said:
paoloh said:
Power flush maybe?
You work for British gas aicmfp
You use terrible forum banter aicmfpetihtbjwwuefotmlaahotff*


*and i claim my five pounds even though i hate the bandwagon jumping wkers who use every flavor of the month lame attempt at humor on this fking forum
Seems a little harsh.

tvradict

Original Poster:

3,829 posts

303 months

Thursday 4th December 2008
quotequote all
thumbup

Turned all the others off and the Cold one isn't cold anymore biggrinbiggrin

I've looked up balancing on the web so i'll try that later. Gonna let this room warm up a bit first!

Cheers
Stuart.

Ferg

15,242 posts

286 months

Thursday 4th December 2008
quotequote all
tvradict said:
thumbup

Turned all the others off and the Cold one isn't cold anymore biggrinbiggrin

I've looked up balancing on the web so i'll try that later. Gonna let this room warm up a bit first!

Cheers
Stuart.
Aim for 11 degrees across the flow and return.

tubbystu

3,846 posts

289 months

Thursday 4th December 2008
quotequote all
Impulse 9 said:
You use terrible forum banter aicmfpetihtbjwwuefotmlaahotff*


*and i claim my five pounds even though i hate the bandwagon jumping wkers who use every flavor of the month lame attempt at humor on this fking forum


Calm down dear, its only an internet forum

tvradict

Original Poster:

3,829 posts

303 months

Thursday 4th December 2008
quotequote all
Thanks for all the help :thumbuo:

All rads now up to a decent temp and the flat is warming nicely. They may not all be set perfectly but they are all about the same warmth which is the main thing.

At least I know roughly what I'm doing now.

Cheers
Stuart.

dirkgently

2,160 posts

260 months

Friday 5th December 2008
quotequote all
Impulse 9 said:
dirkgently said:
paoloh said:
Power flush maybe?
You work for British gas aicmfp
You use terrible forum banter aicmfpetihtbjwwuefotmlaahotff*


*and i claim my five pounds even though i hate the bandwagon jumping wkers who use every flavor of the month lame attempt at humor on this fking forum
As the OP`s question had been answered, I thought I would try to point out that some firms may try to sell a £600 powerflush for a non existent problem, my attempt at humor obviously failed.
For my own part I find the petty minded individuals who have a pop without adding to the debate ruin the forum for me.

Ferg

15,242 posts

286 months

Friday 5th December 2008
quotequote all
dirkgently said:
For my own part I find the petty minded individuals who have a pop without adding to the debate ruin the forum for me.
I find it mildly amusing, but not really on one of the 'asking for help' threads. I can see it getting to the point where people who actually KNOW how to solve these problems (heating or whatever) will think it's just not worth it and then ALL the advice will come from wkers who think they know, but are actually wasting people's time.
I have to say that most of my PH P&H (see what I did there?)advice is done by answering e-mails, Dirk. smile

Captain Cadillac

2,974 posts

216 months

Friday 5th December 2008
quotequote all
Impulse 9 said:
dirkgently said:
paoloh said:
Power flush maybe?
You work for British gas aicmfp
You use terrible forum banter aicmfpetihtbjwwuefotmlaahotff*


*and i claim my five pounds even though i hate the bandwagon jumping wkers who use every flavor of the month lame attempt at humor on this fking forum
You drive a Remapped 335d?

MonkeyHanger

9,267 posts

271 months

Friday 5th December 2008
quotequote all
Ferg said:
I have to say that most of my PH P&H (see what I did there?)advice is done by answering e-mails, Dirk. smile
Very wise.

The vast majority of responses in these threads are misinformed at best, and in many cases bloody dangerous.

The asbestos threads always make me chuckle and that takes some doing having had the "pleasure" of watching my Father waste away due to working with the stuff himself.

gtr-gaz

5,281 posts

275 months

Friday 5th December 2008
quotequote all
MonkeyHanger said:
Ferg said:
I have to say that most of my PH P&H (see what I did there?)advice is done by answering e-mails, Dirk. smile
Very wise.

The vast majority of responses in these threads are misinformed at best, and in many cases bloody dangerous.

The asbestos threads always make me chuckle and that takes some doing having had the "pleasure" of watching my Father waste away due to working with the stuff himself.
You mean, like asbestolux is ok to break up and throw in the skip?!

MonkeyHanger

9,267 posts

271 months

Friday 5th December 2008
quotequote all
gtr-gaz said:
You mean, like asbestolux is ok to break up and throw in the skip?!
That one amongst many wink

SS HSV

9,646 posts

287 months

Friday 5th December 2008
quotequote all
paoloh said:
Power flush fleece maybe?
wink EFA