PLUMBING...Radiator hot at the bottom Only..help
PLUMBING...Radiator hot at the bottom Only..help
Author
Discussion

G20RG B

Original Poster:

2,749 posts

260 months

Friday 13th February 2009
quotequote all
2 of my upstairs radiators are only getting hot at the bottom , I have tried bleeding them with the "key" at the top left but very little air is coming out.

The inlet pipe is very hot and the outlet pipe is very hot as is the bottom of the radiator, but it seems no hot water is rising to the top of the radiator.Have i got an airlock inside the radiator panel?.

Anyone got any suggestions were expecting subzero temperatures over the weekend and one of the radiators is in the kids room so I would realy like to get this sorted.

Any help would be great..

V8mate

45,899 posts

218 months

Friday 13th February 2009
quotequote all
You are Petrol_Penelope AICMFP.


ETA Link

http://pistonheads.com/gassing/topic.asp?h=0&t...

Edited by V8mate on Friday 13th February 16:20

Thudd

3,100 posts

236 months

Friday 13th February 2009
quotequote all
Top up the pressure in the system then try bleeding them again.

Scotfox

582 posts

214 months

Friday 13th February 2009
quotequote all
All see here re balancing the system:-
http://www.pistonheads.com/gassing/topic.asp?h=0&a...

NDA

25,535 posts

254 months

Friday 13th February 2009
quotequote all

Have you bled all the radiators in your house? Go around and do every one if not.

Be patient and ensure that each one is dribbling water from the valve.


GreenV8S

31,012 posts

313 months

Friday 13th February 2009
quotequote all
G20RG B said:
2 of my upstairs radiators are only getting hot at the bottom , I have tried bleeding them with the "key" at the top left but very little air is coming out.
When you say "very little air is coming out" I take it you mean you're getting water out but no air? An air lock in the radiator is the only explanation I can see for it being cold at the top. If it's got limited water flow, usually it's the top that gets warm (heat rises and all that).

dodgyviper

1,213 posts

267 months

Friday 13th February 2009
quotequote all
GreenV8S said:
G20RG B said:
2 of my upstairs radiators are only getting hot at the bottom , I have tried bleeding them with the "key" at the top left but very little air is coming out.
When you say "very little air is coming out" I take it you mean you're getting water out but no air? An air lock in the radiator is the only explanation I can see for it being cold at the top. If it's got limited water flow, usually it's the top that gets warm (heat rises and all that).
Could be sludged up. yummy job

catso

16,373 posts

296 months

Friday 13th February 2009
quotequote all
Are you bleeding it with the pump running or off? I have a radiator that regularly needs bleeding and it will only bleed properly if the pump is off.

Iain328

14,975 posts

235 months

Friday 13th February 2009
quotequote all
G20RG B said:
2 of my upstairs radiators are only getting hot at the bottom , I have tried bleeding them with the "key" at the top left but very little air is coming out.

The inlet pipe is very hot and the outlet pipe is very hot as is the bottom of the radiator, but it seems no hot water is rising to the top of the radiator.Have i got an airlock inside the radiator panel?.

Anyone got any suggestions were expecting subzero temperatures over the weekend and one of the radiators is in the kids room so I would realy like to get this sorted.

Any help would be great..
First thing's first, have you got a combi boiler or a standard one?

if its a combi then you may need to increase the pressure in the system , then bleed, then check the pressure again (which should have dropped when you get the air out for obvious reasons).

If its a standard system with a hot water tank & a header tank then try bleeding it with the pump turned off. In fact in either case, try bleeding it with the pump off.

Edited by Iain328 on Friday 13th February 16:53

G20RG B

Original Poster:

2,749 posts

260 months

Friday 13th February 2009
quotequote all
Right guys,

Thanks for all your help.......ITS SORTED

The pressure in the system was to low just a noch above 0.

I have increased it to 1.5bar and bled the radiators and air came wooshing out and the heat has risen through the radiators...boiling.

Thanks for all your replies especially THUDDbow

Edited by G20RG B on Friday 13th February 18:01

NDA

25,535 posts

254 months

Friday 13th February 2009
quotequote all
Iain328 said:
First thing's first, have you got a combi boiler or a standard one?

if its a combi then you may need to increase the pressure in the system , then bleed, then check the pressure again (which should have dropped when you get the air out for obvious reasons).

If its a standard system with a hot water tank & a header tank then try bleeding it with the pump turned off. In fact in either case, try bleeding it with the pump off.
Which is EXACTLY what I would have said.

Assuming I had that sort of technical knowledge.

And could sum it up neatly in a couple of sentences.

Accurately.

Glad you're toastie again. smile

Iain328

14,975 posts

235 months

Saturday 14th February 2009
quotequote all
G20RG B said:
Right guys,

Thanks for all your help.......ITS SORTED

The pressure in the system was to low just a noch above 0.

I have increased it to 1.5bar and bled the radiators and air came wooshing out and the heat has risen through the radiators...boiling.

Thanks for all your replies especially THUDDbow

Edited by G20RG B on Friday 13th February 18:01
Glad to hear its fixed for the moment. Sadly your next quest might be to investigate why the pressure dropped if it does so again in short order. Keep an eye on it for the next week or two.