More Oil Boiler problems any advice appreciated !!!!
More Oil Boiler problems any advice appreciated !!!!
Author
Discussion

Craphouserat

Original Poster:

1,541 posts

225 months

Wednesday 20th July 2011
quotequote all
The initial message was deleted from this topic on 21 July 2011 at 19:59

Ricky_M

6,618 posts

243 months

Wednesday 20th July 2011
quotequote all
Sounds like it has overheated, but like you said the HL Stat should have stopped the boiler.

Is it pressurised or open vented?

The smell could have been steam escaping from the Automatic Air Vent.

Sometimes, badly sludged up systems can kettle and the AAV is usually the weakest point when they boil up.