Discussion
Afternoon all, I've recently moved and have a Baxi solo 3 PFL 80 fiited.
Since putting the heating on, i've noticed the boiler fires up for 20 secs, stops for 20 secs, then fires, stops, and so on. I looked at the pressure gauge and its .5 as apposed to 1.5-2. Had a look on tinternet and looks like the boiler / system needs topping up from the mains. Is this something I can do or do I need an expert to look at it? Is it safe to use the boiler in the mean time? Any advice welcome. Many thanks, Mark
Since putting the heating on, i've noticed the boiler fires up for 20 secs, stops for 20 secs, then fires, stops, and so on. I looked at the pressure gauge and its .5 as apposed to 1.5-2. Had a look on tinternet and looks like the boiler / system needs topping up from the mains. Is this something I can do or do I need an expert to look at it? Is it safe to use the boiler in the mean time? Any advice welcome. Many thanks, Mark
Should have a filling point somewhere. This may help..........
http://www.acwilgar.co.uk/Boiler-Manual-PDF/Baxi/S...
http://www.acwilgar.co.uk/Boiler-Manual-PDF/Baxi/S...
This is a common issue with sealed systems (combi boilers mostly). There will be a tap near the boiler somewhere, sometimes just one that is operated by a screw driver. Turn this on and you will hear the water going in. Look at the pressure gauge until it os over 1bar say 1.5bar, then turn it off. If it drops again though you may have a leak and will need to look into this.
markbigears said:
Afternoon all, I've recently moved and have a Baxi solo 3 PFL 80 fiited.
Since putting the heating on, i've noticed the boiler fires up for 20 secs, stops for 20 secs, then fires, stops, and so on. I looked at the pressure gauge and its .5 as apposed to 1.5-2. Had a look on tinternet and looks like the boiler / system needs topping up from the mains. Is this something I can do or do I need an expert to look at it? Is it safe to use the boiler in the mean time? Any advice welcome. Many thanks, Mark
Dead PCB.Since putting the heating on, i've noticed the boiler fires up for 20 secs, stops for 20 secs, then fires, stops, and so on. I looked at the pressure gauge and its .5 as apposed to 1.5-2. Had a look on tinternet and looks like the boiler / system needs topping up from the mains. Is this something I can do or do I need an expert to look at it? Is it safe to use the boiler in the mean time? Any advice welcome. Many thanks, Mark
markbigears said:
Hi Peter, so i'm looking for a tap near the boiler not actually on the boiler? As there are 4 pipes going into the bottom of it. Great taste in cars you have 
Thanks very much. Yes the tap is not on the boiler but usually near it underneath.
Edited by markbigears on Thursday 20th October 16:16
dirkgently said:
markbigears said:
Afternoon all, I've recently moved and have a Baxi solo 3 PFL 80 fiited.
Since putting the heating on, i've noticed the boiler fires up for 20 secs, stops for 20 secs, then fires, stops, and so on. I looked at the pressure gauge and its .5 as apposed to 1.5-2. Had a look on tinternet and looks like the boiler / system needs topping up from the mains. Is this something I can do or do I need an expert to look at it? Is it safe to use the boiler in the mean time? Any advice welcome. Many thanks, Mark
Dead PCB.Since putting the heating on, i've noticed the boiler fires up for 20 secs, stops for 20 secs, then fires, stops, and so on. I looked at the pressure gauge and its .5 as apposed to 1.5-2. Had a look on tinternet and looks like the boiler / system needs topping up from the mains. Is this something I can do or do I need an expert to look at it? Is it safe to use the boiler in the mean time? Any advice welcome. Many thanks, Mark