Combi Boiler High Pressure
Author
Discussion

JakeS

Original Poster:

2,270 posts

216 months

Sunday 6th November 2011
quotequote all
My combi boiler has slowly been losing pressure without my knowledge and as of yesterday it would not kick in.
I increased the pressure using the fill flexible pipe that joins the 2 pipes together and turned it of at 1 bar. However the boiler pressure kept increase to 2 bar.

When I put the heating on now the pressure increases to about 2.5 bar

Is this still a safe pressure to use the boiler out or will I need to reduce the pressure. If I need to reduce it what is the best way to do this?

Thanks,


Jake

Crafty_

14,244 posts

231 months

Sunday 6th November 2011
quotequote all
I think all boilers have a puke pipe, so if the pressure is too high it will dump some water/pressure.

On mine the pressure gauge has markings to show when pressure will be too high too low, does yours not have that ?

JakeS

Original Poster:

2,270 posts

216 months

Sunday 6th November 2011
quotequote all
Crafty_ said:
I think all boilers have a puke pipe, so if the pressure is too high it will dump some water/pressure.

On mine the pressure gauge has markings to show when pressure will be too high too low, does yours not have that ?
There are no markings to say it is to high just a pressure gauge. Does the boiler automatically use said puke pipe or is it something that I will have to do?

dirkgently

2,160 posts

262 months

Sunday 6th November 2011
quotequote all
I wouldn't worry about it.smile

JakeS

Original Poster:

2,270 posts

216 months

Sunday 6th November 2011
quotequote all
dirkgently said:
I wouldn't worry about it.smile
After looking at your occupation I shall take your advice and leave it as it is! Is it fine to use as normal?

dirkgently

2,160 posts

262 months

Sunday 6th November 2011
quotequote all
JakeS said:
After looking at your occupation I shall take your advice and leave it as it is! Is it fine to use as normal?
If the only issue is over filling then all should work as normal.

Arthur Jackson

2,111 posts

261 months

Sunday 6th November 2011
quotequote all
It'll discharge out of the safety at or around 3 Bar, otherwise don't worry about it.

cjs

11,733 posts

282 months

Sunday 6th November 2011
quotequote all
If you have lost pressure and had to refill then there may be a problem with the boiler causing over pressurisation and water loss. If you lose pressure again you'll need to find out why.

JakeS

Original Poster:

2,270 posts

216 months

Sunday 6th November 2011
quotequote all
cjs said:
If you have lost pressure and had to refill then there may be a problem with the boiler causing over pressurisation and water loss. If you lose pressure again you'll need to find out why.
Yea I will do. It is a rented property and the Gas certificate runs out in a month so I will get it checked then.

Rickyy

6,618 posts

250 months

Sunday 6th November 2011
quotequote all
Arthur Jackson said:
It'll discharge out of the safety at or around 3 Bar, otherwise don't worry about it.
Hopefully!! Went to a Worcester 28i Junior today, the flexi pipe that leads to the manifold for the expansion vessel and PRV was blocked solid, customer said the pressure gauge had gone past 3 bar and had nearly gone all the way round to zero!

Arthur Jackson

2,111 posts

261 months

Sunday 6th November 2011
quotequote all
Faulty Pressure Relief??

172ff

3,777 posts

226 months

Monday 7th November 2011
quotequote all
Crafty_ said:
I think all boilers have a puke pipe, so if the pressure is too high it will dump some water/pressure.

On mine the pressure gauge has markings to show when pressure will be too high too low, does yours not have that ?
Have a look at this. When it all goes wrong mythbusters style:

http://www.youtube.com/watch?v=rGWmONHipVo


JakeS

Original Poster:

2,270 posts

216 months

Monday 7th November 2011
quotequote all
Pressure has slowly been going down so will have to see if that is the boiler correcting itself or I have a small leak if it goes below 1 bar again I will get a plumber out.

cjs

11,733 posts

282 months

Monday 7th November 2011
quotequote all
There should be an outlet pipe running to the outside of the house, this is where the pressure relief valve discharges water, check to see if any water has been released from that pipe. You may need to tie a plastic bag over the pipe to see if any water comes out.

anonymous-user

85 months

Monday 7th November 2011
quotequote all
2.5 bar sounds about right, have you googled your boiler model/pressure?, its bound to be readily available...

cinnamongirl

2 posts

179 months

Sunday 18th December 2011
quotequote all
British gas engineer left my boiler pressure at 2.5 is that ok. The manual for the boiler says between 1 and 1.5 is the norm. I really felt like he was not being honest with me. He came in with an attitude and was more interested in getting home early as it was the team Xmas night out. When I asked him about the pressure being at 2.5 he said that when the heating is off it will go back down which it hasn't I'm worried that the high pressure is stressing other internal components. There isn't an obvious overflow pipe to release water automatically. The original fault was not lighting so he checked the ignition it was fine so he replaced the ignition card which he had to order at first then magically found one and the boiler started working again. He then dropped a clip down the back of my worktop told me I'd have to get it back or the pipe could burst at any time he drained the boiler then went for a haircut as he wouldn't wait around for me to remove the surrounding cupboard. after cutting gyp rock and pulling out cavity wall insulation I found said clip and called him back he came back from the barbers put the clip on and refilled the boiler to 2.5 and left telling me that it may be another fault and that would be another £100 as it's £100 per fault. Apart from the disgraceful attitude and the mess he left my house in rather than giving me another clip I'm stressing about the pressure being at 2.5 this seems high anyone any ideas??

Rickyy

6,618 posts

250 months

Sunday 18th December 2011
quotequote all
2.5 bar is the higher end of normal working pressure when the boiler us up to temperature. Don't worry though, they can handle much higher pressure than that and it will have a built in pressure relief valve that opens up at 3 bar and releases the pressure to atmosphere.

If you look outside you should see a copper pipe running to the floor or turned back to the wall, this is where the water will discharge.


cinnamongirl

2 posts

179 months

Sunday 18th December 2011
quotequote all
thanks Ricky, there's so much conflicting advice out there. I have visions of the boiler exploding when Santa comes down the chimney and ruining Xmas and what's left of the kitchen.

dirkgently

2,160 posts

262 months

Sunday 18th December 2011
quotequote all
cinnamongirl said:
British gas engineer left my boiler pressure at 2.5 is that ok. The manual for the boiler says between 1 and 1.5 is the norm. I really felt like he was not being honest with me. He came in with an attitude and was more interested in getting home early as it was the team Xmas night out. When I asked him about the pressure being at 2.5 he said that when the heating is off it will go back down which it hasn't I'm worried that the high pressure is stressing other internal components. There isn't an obvious overflow pipe to release water automatically. The original fault was not lighting so he checked the ignition it was fine so he replaced the ignition card which he had to order at first then magically found one and the boiler started working again. He then dropped a clip down the back of my worktop told me I'd have to get it back or the pipe could burst at any time he drained the boiler then went for a haircut as he wouldn't wait around for me to remove the surrounding cupboard. after cutting gyp rock and pulling out cavity wall insulation I found said clip and called him back he came back from the barbers put the clip on and refilled the boiler to 2.5 and left telling me that it may be another fault and that would be another £100 as it's £100 per fault. Apart from the disgraceful attitude and the mess he left my house in rather than giving me another clip I'm stressing about the pressure being at 2.5 this seems high anyone any ideas??
To be honest he probably didnt have another clip to give you, but if you take crap like that I am willing to take you on as a customer.smile