Boiler - Condensate pump?
Author
Discussion

wainy

Original Poster:

800 posts

274 months

Thursday 17th November 2011
quotequote all
Its getting towards winter and one thing on the todo list if the condensate pipe for the darn condensing boiler.

There are 2 options: Condensate pump through loft and into soil pipe or a "heater coil"

Has anyone any experience of either of these and what are the benefits / problems and relative costs (installation / running?)

Quite like the idea of the pump as I am sure looking at the current "pipe" going outdoor it looks as its bowed and not installed properly and hate it on the outside.

Cheers

Gingerbread Man

9,173 posts

244 months

Thursday 17th November 2011
quotequote all
Can you upsize the external pipe to 32mm?

Run heat trace wire?

wainy

Original Poster:

800 posts

274 months

Thursday 17th November 2011
quotequote all
I would say the external pipe is 32mm or larger coming from a 15/22mm pipe inside

andySC

1,400 posts

189 months

Thursday 17th November 2011
quotequote all
I'd go with the Trace Wire option. I've fitted a few in the last couple of months & installation is pain free & quite straightforward. Condensate pumps can be a touch on the noisey side when they discharge but again, simple enough to install.

Let's just hope the Winter isn't as bleak as last year/year before!

Gingerbread Man

9,173 posts

244 months

Thursday 17th November 2011
quotequote all
wainy said:
I would say the external pipe is 32mm or larger coming from a 15/22mm pipe inside
Same diameter as your basin waste?
Has it frozen at this diameter before?

It should be upped from 22mm as if leaves the boiler to 32mm if it will be unlagged before it goes outside. If terminated into a drain, it should be routed below the grating to prevent wind chill not helping the matter.

Inside is preferable but not always easily doable.

wainy

Original Poster:

800 posts

274 months

Thursday 17th November 2011
quotequote all
It seems that from the boiler to external wall is 22mm and fitted to a 32mm down to drain. Frozen a few times and thinking an internal pump would be the way forward (rather than rip up floor boards etc)