Question for electrician (amount of lights on 6A circuit)
Question for electrician (amount of lights on 6A circuit)
Author
Discussion

matts4

Original Poster:

2,117 posts

222 months

Monday 21st November 2011
quotequote all
OK, I currently have on 1 circuit:

6 x spotlight at 60w (utility room)
2 x 60w lights (toilet and larder)
4 x 58w flourescent tubes (garage ceailing)
2 x 150w halogen floodlights (security lights in my garage for if I walk in when its dark)
1 x 500w halogen light (on outside wall under my carport)

I know wish to add another floodlight under my carport (to get good light when washing it in the dark) but I think this maybe too much for the lighting circuit.

My calculations would put the current load (if all were on at the same time at 1512 watts (or 6.2 amps) excluding the new flood light, and this has never caused an issue.

I appreciate that I shouldn't add the 500w flood into the circuit, but am hoping it would be negated if I replaced the bulbs in both of the 500w floods with 250w. (they'd be bright enough)

That way the load will be no bigger than now. Is this correct?

My alternative is to take just the floodlights (2 x 150w and 2 x 500w) and put them through the spare space on the fuse box which just happens to be handily located in the garage.

I wouldn't know where to start in wiring it there, so any idea what cost would this be to get some one to do it ?

Thanks
Matt

matts4

Original Poster:

2,117 posts

222 months

Tuesday 22nd November 2011
quotequote all
Afternoon bump for the electricians...

cjs

11,729 posts

282 months

Tuesday 22nd November 2011
quotequote all
230v x 6a = 1380w

Yes you're right on the limit now. Changing the floods for 300w would be a good idea plus it would save £'s on electric.

If you can wire the floods of a new circuit in the garage that would also be a good idea, easy to do if you are competent. You would need some 1.5mm T&E cable and a 6a breaker for the distribution board. I would also add a switch or switched spur in the circuit so you can turn them off easily rather than switching off the breaker.

Not sure on a cost for an Electrician to do the work, it should not take more than half a day if the cables are easy to run in.

Edited by cjs on Tuesday 22 November 15:43


Edited by cjs on Tuesday 22 November 15:43


Edited by cjs on Tuesday 22 November 15:47

matts4

Original Poster:

2,117 posts

222 months

Tuesday 22nd November 2011
quotequote all
Many thanks.

I've now got the 4 floods all wired up and the end of the cable is now at the fuse box/consumer unit.
I'd feel better getting an electrician into do the last bit, so will look into that later this week.


Solitude

1,902 posts

206 months

Tuesday 22nd November 2011
quotequote all
10A breaker ?

matts4

Original Poster:

2,117 posts

222 months

Wednesday 23rd November 2011
quotequote all
Prett sure i'd need to uprate the other cable to make that an option, no?


cjs

11,729 posts

282 months

Wednesday 23rd November 2011
quotequote all
matts4 said:
Many thanks.

I've now got the 4 floods all wired up and the end of the cable is now at the fuse box/consumer unit.
I'd feel better getting an electrician into do the last bit, so will look into that later this week.
Do all your floods have PIR's? If not you should wire the ones with PIR's on a circuit and the ones without on a separate circuit, with a switch in line to turn them on and off.

matts4

Original Poster:

2,117 posts

222 months

Wednesday 23rd November 2011
quotequote all
Yep, they all have PIR's.

Ideally i'd have the 2 external ones on a seperate switch to enable them to switched on for the time I need them when washing the car (if you switch them on off back on within 10 seconds, they stay on).

I'll see what I can muster with the electrician when he comes to wire it into the cosnumer unit next Sat