Help! Central heating driving me mad....
Discussion
Basic issue is I can't get any heat /flow upstairs. Thought it was just unbalanced, but it's worse than that. I just don't get any flow upstairs, despite the fact that the split between the two circuits (up/down) is at first floor level. Roughly it's laid out like this (with rough temps):

Everything is fine downstairs.
There's 4 rads upstairs, highest inlet pipe temp is 52 deg. None of the rads get very warm (around 30 deg).
Done a bucket test on all of them (rads off, pipes flushed through and rads flushed). Do get water flow when filling loop is connected. System has been drained down / flushed a million times in the last couple of years.
1930's house. Had an open system I think, now converted to a closed system / combi boiler. Can't adjust pump speed on boiler I don't think (baxi 80 eco).
Central heating is a bodge job I think. Drain point is bosched out of an airbrick sticking out of the front of the house about 3" (I didn't know it was there as there's a bush in front).
There's a random hot pipe in the loft sticking through the loft insulation from the old installation.
Any ideas what to do? Do you think there might be some kind of blockage in the manifold upstairs? Air? Other ideas?
Everything is fine downstairs.
There's 4 rads upstairs, highest inlet pipe temp is 52 deg. None of the rads get very warm (around 30 deg).
Done a bucket test on all of them (rads off, pipes flushed through and rads flushed). Do get water flow when filling loop is connected. System has been drained down / flushed a million times in the last couple of years.
1930's house. Had an open system I think, now converted to a closed system / combi boiler. Can't adjust pump speed on boiler I don't think (baxi 80 eco).
Central heating is a bodge job I think. Drain point is bosched out of an airbrick sticking out of the front of the house about 3" (I didn't know it was there as there's a bush in front).
There's a random hot pipe in the loft sticking through the loft insulation from the old installation.
Any ideas what to do? Do you think there might be some kind of blockage in the manifold upstairs? Air? Other ideas?
Right, ripped up some floorboards upstairs...
There's three 22mm pipes that run alongside each other straight up into the loft. Two have been joined together, in a loop (with a bleed point), the other simply terminates where the tank used to be(no idea what this is). The loop is around the 70ish deg mark (central heated loft!), the other around 35 deg.
I think this is a big loop on the flow and returns (explains the lack of temp drop when the pipes loop upstairs). I think the upstairs rads are in parallel to this loop with at least two in series. I assume then that the flow is ignoring these upstairs rads and taking the path of least resistance back downstairs.
Updated:

There's three 22mm pipes that run alongside each other straight up into the loft. Two have been joined together, in a loop (with a bleed point), the other simply terminates where the tank used to be(no idea what this is). The loop is around the 70ish deg mark (central heated loft!), the other around 35 deg.
I think this is a big loop on the flow and returns (explains the lack of temp drop when the pipes loop upstairs). I think the upstairs rads are in parallel to this loop with at least two in series. I assume then that the flow is ignoring these upstairs rads and taking the path of least resistance back downstairs.
Updated:
Bit of a strange one! From your first picture, it looks like a one pipe system. Do the upstairs rads heat up if you close off the downstairs ones?
First thing I would do is install a gate valve into that loop in the attic, close it down and see if that helps matters. It could be a flow and return linked together, heat will take the easiest path, it could be by passing the rads altogether.
First thing I would do is install a gate valve into that loop in the attic, close it down and see if that helps matters. It could be a flow and return linked together, heat will take the easiest path, it could be by passing the rads altogether.
Rickyy said:
Bit of a strange one! From your first picture, it looks like a one pipe system. Do the upstairs rads heat up if you close off the downstairs ones?
I'm not sure the drawing can be correct - if it was single pipe I woudn't expect the flow and return for the upstairs rads to be connected to the same pipe. Our house was single pipe and it just flowed in a simple continuous loop.Thanks for the feedback guys. I'll try a valve in the loft loop, though I think it may stop all flow if it's a single pipe system, which I think it is now, or at least a mix. Oddly, if I shut down all the downstairs rads and leave one upstairs open, the boiler shuts down with lack of flow, hence why i'm wondering if it's a mix of single/double pipe.
Going to get a few rad valves to replace the cheap trv's I've (and the previous owner) fitted recently, as I don't think they will be single pipe compatible. I'ts never been much cop...
Going to get a few rad valves to replace the cheap trv's I've (and the previous owner) fitted recently, as I don't think they will be single pipe compatible. I'ts never been much cop...
VxDuncan said:
Thanks for the feedback guys. I'll try a valve in the loft loop, though I think it may stop all flow if it's a single pipe system, which I think it is now, or at least a mix. Oddly, if I shut down all the downstairs rads and leave one upstairs open, the boiler shuts down with lack of flow, hence why i'm wondering if it's a mix of single/double pipe.
Going to get a few rad valves to replace the cheap trv's I've (and the previous owner) fitted recently, as I don't think they will be single pipe compatible. I'ts never been much cop...
One-pipe or not, you should still be able to turn radiators off. If it IS one-pipe the radiators should all be situated above the pipe run.Going to get a few rad valves to replace the cheap trv's I've (and the previous owner) fitted recently, as I don't think they will be single pipe compatible. I'ts never been much cop...
I'd say so. In a one-pipe system both ends of the radiator are teed off the pipe VERTICALLY allowing gravity to take the heat into, and back out of, the radiator. (This is why when people have the bright idea of moving a raiator across the room it seldom works properly. t
ts introduce restricting valves in the pipework to force it to the rad which in turn ruins the circulation.)
In your case it looks like a short circuit through the roof space pipework is causing the grief.
ts introduce restricting valves in the pipework to force it to the rad which in turn ruins the circulation.)In your case it looks like a short circuit through the roof space pipework is causing the grief.
VxDuncan said:
Thanks for the feedback guys. I'll try a valve in the loft loop, though I think it may stop all flow if it's a single pipe system,
If you've drawn it correctly, then yes it will (stop the flow).Again, assuming it's drawn correctly, if you put a valve in the pipe between where the upstairs flow and return is taken off then that would force water around the upstairs loop.
Are you sure they're not both flows, and the returns are somewhere else? Our house had the boiler in the middle of the house, with flow under the floor, then T'd to two loops, one to the front half of the house and the other to the back. At the front and back of the house pipes then went upstairs, around the front and back upstairs rads, and then came together again in the middle of the house in a T and then dropped back down to the boiler.
Single pipe systems work a bit like electrical resistors - put two in parallel (ie the rad and the pipe) and they'll share the flow but if something restricts the flow into the rad then the water will just take the path of least resistance and all of it will carry on along the pipe. I don't think any old thermostatic rad valve will suit a one pipe system for this reason.
Edited by Deva Link on Tuesday 6th December 10:45
I think it's drawn correctly, at least as far as I know...
Have removed the cool centre pipe upstairs that as suspected wasn't doing anything. Now just have the single pipe system loop I think. Gunna trim the loft loop of at first floor level when I have more fittings. Replacing one of the upstairs TRVs with a manual valve hasn't worked yet - need to replace them all in the upstairs loop I think (They MAY even be in series, I know one is...).
Have removed the cool centre pipe upstairs that as suspected wasn't doing anything. Now just have the single pipe system loop I think. Gunna trim the loft loop of at first floor level when I have more fittings. Replacing one of the upstairs TRVs with a manual valve hasn't worked yet - need to replace them all in the upstairs loop I think (They MAY even be in series, I know one is...).
Loop up to the loft cut off and re joined at first floor level. Valve fitted in upstairs circuit to proportion flow upstairs / downstairs by forcing flow thorugh the upstairs rads rather than bypass them and go straight downstairs in the single pipe loop.
Seems I have a single pipe system upstairs, and a dual pipe system downstairs. Good fun.
But I'm no longer central heating the loft, can get it toasty upstairs so happy. Just need to find the best balance up / down and then balance the lot. Then sort out the noise as it currently makes a racket (general flow noises, pipes moving against joists and the occasional groan from the boiler (TRVs?). And then put some inhibitor in when I've finished playing.
Thanks for all the help guys. Really helped a lot.
Seems I have a single pipe system upstairs, and a dual pipe system downstairs. Good fun.
But I'm no longer central heating the loft, can get it toasty upstairs so happy. Just need to find the best balance up / down and then balance the lot. Then sort out the noise as it currently makes a racket (general flow noises, pipes moving against joists and the occasional groan from the boiler (TRVs?). And then put some inhibitor in when I've finished playing.
Thanks for all the help guys. Really helped a lot.
Gassing Station | Homes, Gardens and DIY | Top of Page | What's New | My Stuff


