Hot water not that hot anymore.......
Hot water not that hot anymore.......
Author
Discussion

dave_s13

Original Poster:

14,032 posts

300 months

Wednesday 14th December 2011
quotequote all
Anyone shed any light on this little issue.

Boiler is a Vokera Compact 25HE
http://vokera.co.uk/wp-content/uploads/2009/04/com...

This issue has only really become really apparant with the recent colder weather.

We have 2x Mira thermostatic showers, one of which is a case of just turning a lever to set the temp and it automatically mixes the hot and cold as it sees fit. The other has 2 controls, one for temp, one for flow rate.

The first one has recently started to only really get luke warm and the other only gets hot if you turn the flow rate down a bit. To get a hot shower in the one with no flow control you have to run the cold tap in the sink at the same time (I've tried adjusting the thermo cartridge in it with no effect).

Also filling the bath needs the hot tap flow rate to be turned down a touch or it just runs warmish.

We are "blessed" with very high pressure cold water mains in our house. It comes out like a bloody pressure washer!! I'm thinking that given the recent cold weather the water is entering the boiler at such a high flow rate that it's making it's journey through the heat exchanger too quickly, hence not picking up enough heat? Is that possible or am I just talking bks?

I've looked at that technical manual and see that you can get varying degrees of flow restrictor and wonder if this might work. I'd be happy to lose a bit of flow rate to avoid having to mess about running other taps or regulating the tap to get a hot supply. Or, can you just turn up the gas burner to MAX and hope for the best? Oh the HW stat on the front of the boiler is set to max BTW.

Any thoughts welcome.


Edited by dave_s13 on Wednesday 14th December 10:47

GreenDog

2,261 posts

223 months

Wednesday 14th December 2011
quotequote all
Is it not just that the water coming in from the main is a few degrees colder now and you need to turn up the heat on the boiler and shower to compensate ? As I understand it each will only heat the water to a certain temp above incoming the incoming water temp.

cjs

11,732 posts

282 months

Wednesday 14th December 2011
quotequote all
I have a combi and there is a big difference between HW temps in the summer and winter, I have to run HW only when filling a bath in the winter.

Why not try reducing the incoming water, you could use the main stop cock, this will also limit the CW flow to the showers.

Deva Link

26,934 posts

276 months

Wednesday 14th December 2011
quotequote all
cjs said:
Why not try reducing the incoming water, you could use the main stop cock,
I do this anyway in my house, as our mains pressure and flow is tremendous. Neighbours have had trouble with washing machine hoses blowing off etc.

We have an elec shower and the mains water temp makes a big difference, the flow rate really has to be slowed as the weather has cooled.

It is possible the boiler could have a fault - my in-laws moved into a house with a Worcester combi which was hopeless at producing hot water. Turned out the diverter valve wasn't diverting to the hot water circuit. Time how long it takes to fill a bucket with hot water and you can figure out if it's up to spec.

dave_s13

Original Poster:

14,032 posts

300 months

Wednesday 14th December 2011
quotequote all
Deva Link said:
cjs said:
Why not try reducing the incoming water, you could use the main stop cock,
I do this anyway in my house, as our mains pressure and flow is tremendous. Neighbours have had trouble with washing machine hoses blowing off etc.

.
Good idea. I'll try that first.

mk1fan

10,919 posts

256 months

Wednesday 14th December 2011
quotequote all
How about fitting a pressure regulating valve?

ETA: As already said instantaeous water heaters only heat the water by a certain amount over the incoming temperature. The bigger the heater, the higher temp it can acheive. Factor in mis matched [to the unit] flow and pressure rates and you can end up with very poor performance.

Edited by mk1fan on Wednesday 14th December 12:24

cjs

11,732 posts

282 months

Wednesday 14th December 2011
quotequote all
dave_s13 said:
Good idea. I'll try that first.
I have mine turned down to about half to regulate the pressure, stops the pipes banging and stops water splashing everywhere when I turn a tap on!

dave_s13

Original Poster:

14,032 posts

300 months

Wednesday 14th December 2011
quotequote all
mk1fan said:
How about fitting a pressure regulating valve?

ETA: As already said instantaeous water heaters only heat the water by a certain amount over the incoming temperature. The bigger the heater, the higher temp it can acheive. Factor in mis matched [to the unit] flow and pressure rates and you can end up with very poor performance.

Edited by mk1fan on Wednesday 14th December 12:24
Thing is though, if you reduce the flow rate by 25-30% (by not opening a tap fully), it runs hot. If you reduce it further it gets fackin really hot! You could make a brew with it.

So, to say the boiler will only every heat the water to (incoming water temp) + (a finite figure) seems inaccurate to me. The temp at the outlet is obviously significantly effected by flow rate too....no??

stargazer30

1,722 posts

197 months

Wednesday 14th December 2011
quotequote all
Also Volkera boilers are crap. Ours is the same come winter its not up to the job. Just wait till it gets really cold, the outlet pipe freezes and it goes off (ours does every year)


cjs

11,732 posts

282 months

Wednesday 14th December 2011
quotequote all
stargazer30 said:
Also Volkera boilers are crap. Ours is the same come winter its not up to the job. Just wait till it gets really cold, the outlet pipe freezes and it goes off (ours does every year)
To be fair the outlet pipe has been incorrectly installed, you can't blame the boiler for that.

dave_s13

Original Poster:

14,032 posts

300 months

Wednesday 14th December 2011
quotequote all
cjs said:
stargazer30 said:
Also Volkera boilers are crap. Ours is the same come winter its not up to the job. Just wait till it gets really cold, the outlet pipe freezes and it goes off (ours does every year)
To be fair the outlet pipe has been incorrectly installed, you can't blame the boiler for that.
They ALL seem to do it if it gets cold enough though, regardless of condensate pipe size/material. Fortunatley mine is at ground level so a doddle to get to and apply the kettle to.

I think all combi boilers are ssmilehit really, they all seem to be a liability.

I'm fully expecting it to break down over winter at some point smile

dave_s13

Original Poster:

14,032 posts

300 months

Wednesday 14th December 2011
quotequote all
mk1fan said:
How about fitting a pressure regulating valve?[/footnote]
Dumb question time.

How does the operation of a PRV differ to the result of just turning down the mains water stop tap a few turns??

Gingerbread Man

9,173 posts

244 months

Wednesday 14th December 2011
quotequote all
dave_s13 said:
mk1fan said:
How about fitting a pressure regulating valve?[/footnote]
Dumb question time.

How does the operation of a PRV differ to the result of just turning down the mains water stop tap a few turns??
Pressure reducing valve reduces pressure. Winding the stop cock in a few turns reduces flow, not pressure.

dave_s13

Original Poster:

14,032 posts

300 months

Wednesday 14th December 2011
quotequote all
Well doing just that seems to have sorted it.

Shower is now nice and hot as is the bath tap on full pelt. Still plenty of flow at both too.

cjs

11,732 posts

282 months

Wednesday 14th December 2011
quotequote all
Bloody hell that's my second result of the day!

Arthur Jackson

2,111 posts

261 months

Wednesday 14th December 2011
quotequote all
dave_s13 said:
Well doing just that seems to have sorted it.

Shower is now nice and hot as is the bath tap on full pelt. Still plenty of flow at both too.
The boiler should have a cold water throttle to avoid having to do that, sounds like the heating engineer couldn't be bothered.

Arthur Jackson

2,111 posts

261 months

Wednesday 14th December 2011
quotequote all
dave_s13 said:
I think all combi boilers are ssmilehit really,
Yup. People still get them fitted though. confused

mk1fan

10,919 posts

256 months

Wednesday 14th December 2011
quotequote all
dave_s13 said:
So, to say the boiler will only every heat the water to (incoming water temp) + (a finite figure) seems inaccurate to me. The temp at the outlet is obviously significantly effected by flow rate too....no??
It may seem inaccurate to you but it doesn't stop it being true. There is a limit to how much energy an instantaeous heater can pass into the water flowing through it.

This limit is determined by the power of the heater, the flow of the water and the time the water is exposed to the heat source.

Further to this if the temperature of the incoming water is a lot lower then the resultant temperature is going to be lower. Simple science really. If you put X amount of energy into water then you'll get a rise in temperature of Y degrees.

Y maybe a constant rise - lets say 20 degrees. So, if the incoming temp is 5 degrees then the outgoing temp will be 25 degrees. If the incoming temp rises to 20 degrees then the outgoing temp is 40 degrees.

If to acheive the temp you require you need to reduce the flow down to a level that it takes too long to deliver the water then the instanteneuos heater is undersized.

Gingerbread Man

9,173 posts

244 months

Wednesday 14th December 2011
quotequote all
mk1fan said:
dave_s13 said:
So, to say the boiler will only every heat the water to (incoming water temp) + (a finite figure) seems inaccurate to me. The temp at the outlet is obviously significantly effected by flow rate too....no??
It may seem inaccurate to you but it doesn't stop it being true. There is a limit to how much energy an instantaeous heater can pass into the water flowing through it.

This limit is determined by the power of the heater, the flow of the water and the time the water is exposed to the heat source.

Further to this if the temperature of the incoming water is a lot lower then the resultant temperature is going to be lower. Simple science really. If you put X amount of energy into water then you'll get a rise in temperature of Y degrees.

Y maybe a constant rise - lets say 20 degrees. So, if the incoming temp is 5 degrees then the outgoing temp will be 25 degrees. If the incoming temp rises to 20 degrees then the outgoing temp is 40 degrees.

If to acheive the temp you require you need to reduce the flow down to a level that it takes too long to deliver the water then the instanteneuos heater is undersized.
35 degree rise.

Deva Link

26,934 posts

276 months

Wednesday 14th December 2011
quotequote all
dave_s13 said:
Thing is though, if you reduce the flow rate by 25-30% (by not opening a tap fully), it runs hot. If you reduce it further it gets fackin really hot! You could make a brew with it.

So, to say the boiler will only every heat the water to (incoming water temp) + (a finite figure) seems inaccurate to me. The temp at the outlet is obviously significantly effected by flow rate too....no??
Yes, it is affected by the flow, but it strikes me that it shouldn't get as hot as you describe. I'd be amazed if there isn't a sensor on the output that limits the temp. I know on the Worcester combi the burner comes on at full power but then modulates down to limit the output temp.