Any plumbers out there? Mate replaced a leaking ladder towel in bathroom. Now it doesnt get hot? I've bled it, just water comes out. As i bleed it the rail warms up, close the valve, and its cold again. I've shut off all the other rads, and left it for 5 mins, nothing.

Any ideas? Other than starting a small fire in the bathroom?

Arthur Jackson

2,111 posts

261 months

Monday 19th December 2011
quotequote all
Air lock in the return, I reckon. Close all other rads, any bypasses and put it on CH if you have a cylinder. If that fails, draw water from the vent down a hose alternately opening flow and return valves.

dickymint

29,278 posts

289 months

Monday 19th December 2011
quotequote all
Give your mate a good kicking!

dirty boy

14,879 posts

240 months

Tuesday 20th December 2011
quotequote all
Arthur Jackson said:
Air lock in the return, I reckon. Close all other rads, any bypasses and put it on CH if you have a cylinder. If that fails, draw water from the vent down a hose alternately opening flow and return valves.
Would this work if you had a combi?

I've got one rad in the kitchen that doesn't get hot. The pipe at one end is 'luke warm' but the other end it is stone cold.

It's also been bled and is fine in that respect.

thegman

1,928 posts

235 months

Tuesday 20th December 2011
quotequote all
Does it have a TRV? Could be stuck closed

annodomini2

6,974 posts

282 months

Tuesday 20th December 2011
quotequote all
Has he closed off the downstream valve to do the work and not reset it, i.e. is it closed or wide open? As you will get no heat as a result.


russ_a

4,732 posts

242 months

Tuesday 20th December 2011
quotequote all
Could just need balancing