Combi Boiler won't maintain hot water temp
Discussion
We have a 4 year old Worcester Bosch 30Si. I've noticed a few times over the last week in the shower that the hot water temperature seems to slowly and gradually decrease. To the point I had the temp on max by the end of a 10/15 minute shower, and the water is only warm. The CH seems to be unaffected.
I have reset the boiler and it stopped doing it, but I'm guessing there must be some sort of fault for it to have happened at all.
I spoke to our local heating engineer. He said as it is not currently doing it, I'll have to wait for the fault to start again before he comes out to have a look.
I've had a look online a cant see this fault mentioned anywhere. Would this be something anyone has seen before? Dont fancy suddenly losing my boiler this time of year!
I have reset the boiler and it stopped doing it, but I'm guessing there must be some sort of fault for it to have happened at all.
I spoke to our local heating engineer. He said as it is not currently doing it, I'll have to wait for the fault to start again before he comes out to have a look.
I've had a look online a cant see this fault mentioned anywhere. Would this be something anyone has seen before? Dont fancy suddenly losing my boiler this time of year!
Did you have heating on at the time?
Was the dishwasher\ washing machine or anything that takes water on at the time
Does it have some kind of eco button?
Did you have the control turned up enough? On our worcester bosch unless I have it turned above 4 on the heat setting it can go cold when running a bath or go a bit odd
Was the dishwasher\ washing machine or anything that takes water on at the time
Does it have some kind of eco button?
Did you have the control turned up enough? On our worcester bosch unless I have it turned above 4 on the heat setting it can go cold when running a bath or go a bit odd
Our Worcester boiler is currently doing something a bit similar. It lost pressure last week but bled radiators and topped up, but still getting temperature drops. CH seems to be fine. Don't think it's on eco, "heat setting" is set to 6.
Not much help I'm afraid, but following with interest.
Not much help I'm afraid, but following with interest.
I have exactly this issue at my GF's apartment she rents out.
WB 25i installed 3 weeks ago (not a typo!!) to replace an old and unreliable combi, heating is fine but tenant reported the water temp up and down ... suddenly started this weekend.
When I visited, I could see the heating pressure was at 3 bar so bled the rads and they were full of air. Had to add water to raise the pressure to get all the air out. This won't help but I don't think this is the underlying issue. Will add more inhibitor when this is all sorted.
When I run a tap, the blue light on the boiler remains on and I've checked in the engineering menu and the boiler acknowledges there is a constant demand for water with the tap on but the boiler still shuts down after maybe 60 seconds then starts back up again...hence the increase and decrease in water temp. I don't know why the boiler shuts down after a minute but some have said it maybe the heater exchange is blocked or limited flow.
I lowered the water temp on the boiler to about 40c which seemed to improve the situation but the water temp output is still raising and lowering...during the test there is no heating on, no water demand elsewhere so the only demand is the tap I run.
I have a WB engineer attending today at some point so I'll report back on what he reports
WB 25i installed 3 weeks ago (not a typo!!) to replace an old and unreliable combi, heating is fine but tenant reported the water temp up and down ... suddenly started this weekend.
When I visited, I could see the heating pressure was at 3 bar so bled the rads and they were full of air. Had to add water to raise the pressure to get all the air out. This won't help but I don't think this is the underlying issue. Will add more inhibitor when this is all sorted.
When I run a tap, the blue light on the boiler remains on and I've checked in the engineering menu and the boiler acknowledges there is a constant demand for water with the tap on but the boiler still shuts down after maybe 60 seconds then starts back up again...hence the increase and decrease in water temp. I don't know why the boiler shuts down after a minute but some have said it maybe the heater exchange is blocked or limited flow.
I lowered the water temp on the boiler to about 40c which seemed to improve the situation but the water temp output is still raising and lowering...during the test there is no heating on, no water demand elsewhere so the only demand is the tap I run.
I have a WB engineer attending today at some point so I'll report back on what he reports
Yes CH running at the time, nothing taking any water supply though. Both CH & HW are set to 5 (from memory). ECO setting is on. Pressure at 1.5bar. These are the same settings as per the last 4 years, and it's the first time I've seen the problem, so I suspect there is a fault appeared somewhere.
I would have thought the problem would have remained after reset if there was a heat exchange scaliing up.
Just thinking it's a thermostatic Mira shower, problem potentially in thermo-valve...
You haven't lived till you've spent 15 minutes daydreaming in the shower. Only bit of peace and quiet I get all day...
I would have thought the problem would have remained after reset if there was a heat exchange scaliing up.
Just thinking it's a thermostatic Mira shower, problem potentially in thermo-valve...
You haven't lived till you've spent 15 minutes daydreaming in the shower. Only bit of peace and quiet I get all day...
Have you got a mixer tap elsewhere in the house?
if so turn it to full hot even when it's off, they have a habit of bleeding through one side to the other. If that's happening then the water flow from another tap/shower might not be enough to keep the boiler firing. Happens out our house if the bath mixer is left to cold, even the kitchen sink won't stay hot
if so turn it to full hot even when it's off, they have a habit of bleeding through one side to the other. If that's happening then the water flow from another tap/shower might not be enough to keep the boiler firing. Happens out our house if the bath mixer is left to cold, even the kitchen sink won't stay hot
scottdm3 said:
If it happens at every outlet its probably the boiler
If it only happens at the shower its probably the shower at fault
Exactly this .... in my case it was the same result on taps and the shower.If it only happens at the shower its probably the shower at fault
WB engineer came today and replaced the secondary heat exchanger due to blocking and all working ok now.
I had a similar experience with our older model 24cdi.
I eventually tracked it down to a split in one of the small silicone pipes inside the boiler.
Shame it only comes in 5m when I only needed 5cm, but luckily they showed pity on me at the plumbers merchants.
Worth a look as it saved me replacing the boiler after the Worcester approved plumber wanted to replace the whole boiler.
I eventually tracked it down to a split in one of the small silicone pipes inside the boiler.
Shame it only comes in 5m when I only needed 5cm, but luckily they showed pity on me at the plumbers merchants.
Worth a look as it saved me replacing the boiler after the Worcester approved plumber wanted to replace the whole boiler.
Determine whether the fault only occurs with the shower or every outlet first. It's quite common for thermostatic cartridges to scale up.
If it is on every outlet, it's most likely a blocked plate heat exchanger. When they get blocked, the heated water from the the main heat exchanger can't transfer heat quick enough to the domestic water via the plate heat exchanger, so it overheats and cuts the burner. Temperature drops and the cycle repeats.
If it is on every outlet, it's most likely a blocked plate heat exchanger. When they get blocked, the heated water from the the main heat exchanger can't transfer heat quick enough to the domestic water via the plate heat exchanger, so it overheats and cuts the burner. Temperature drops and the cycle repeats.
Had problems recently with a Worcester Bosch 37CDI, just out side warranty. Was made aware that Worcester Bosch do a one charge call out fee to include labour and parts for £275 inc vat. Telephone number is 0330 123 9339. Does not cover, back plate, tank or if uneconomical to repair where they will just charge call out fee.
Had a leaking primary heat exchanger, new one fitted and was charged £126 labour as this part has 10 year warranty for part not labour. (Cost of part I priced up at £480) Couple of days later system was over pressurising and losing pressure via prv outlet called them back and agreed to revisit and charge balance of original £275 fee (£149)
Expansion vessel replaced, and now all running perfectly. Advantage is that they carry all spares on the van so no return visit.
Well worth it for issues I had, appointment within two days of booking. Head and shoulders above experience I had with a couple of local recommended plumbers, some of whom could not be bothered to turn up as arranged, including a Worcester Bosch approved installer.
May be of interest if you have an issue where parts prices are expensive
Had a leaking primary heat exchanger, new one fitted and was charged £126 labour as this part has 10 year warranty for part not labour. (Cost of part I priced up at £480) Couple of days later system was over pressurising and losing pressure via prv outlet called them back and agreed to revisit and charge balance of original £275 fee (£149)
Expansion vessel replaced, and now all running perfectly. Advantage is that they carry all spares on the van so no return visit.
Well worth it for issues I had, appointment within two days of booking. Head and shoulders above experience I had with a couple of local recommended plumbers, some of whom could not be bothered to turn up as arranged, including a Worcester Bosch approved installer.
May be of interest if you have an issue where parts prices are expensive
Just for an update, the boiler was serviced today.
It turns out we have low gas pressure at the meter. They called the supply company who will (hopefully) be out to repair within 2 hours. Apparently it's an emergency with young children in the house.
With the shower running, the pressure drops to 9mBar. Should be around 21.
The problem could not be replicated at the taps, because the aerated tap water use a lower flow rate to the shower. The dropping gas pressure resulted in the slowly reducing temperature. No fault with the boiler at all.
Cheers all.
It turns out we have low gas pressure at the meter. They called the supply company who will (hopefully) be out to repair within 2 hours. Apparently it's an emergency with young children in the house.
With the shower running, the pressure drops to 9mBar. Should be around 21.
The problem could not be replicated at the taps, because the aerated tap water use a lower flow rate to the shower. The dropping gas pressure resulted in the slowly reducing temperature. No fault with the boiler at all.
Cheers all.
Pamoothican said:
I had a similar experience with our older model 24cdi.
I eventually tracked it down to a split in one of the small silicone pipes inside the boiler.
Shame it only comes in 5m when I only needed 5cm, but luckily they showed pity on me at the plumbers merchants.
Worth a look as it saved me replacing the boiler after the Worcester approved plumber wanted to replace the whole boiler.
Can you elaborate please what you mean by silicon pipe which pipe and where where on the boiler did you find it as I have the same problem hopefully this thread will reach you.I eventually tracked it down to a split in one of the small silicone pipes inside the boiler.
Shame it only comes in 5m when I only needed 5cm, but luckily they showed pity on me at the plumbers merchants.
Worth a look as it saved me replacing the boiler after the Worcester approved plumber wanted to replace the whole boiler.