Low water pressure on Ideal logic 30
Discussion
Hi,
I posted on here a few months ago regarding a different problem with my Ideal Logic 30 boiler and a very kind person helped with their suggestion so I'm hoping for the same again please! Since just before Christmas the boiler keeps losing water pressure, initially with weeks in between however now it requires the pressure increasing a few times per week, as it literally drops completely leaving us without heating or hot water. There are no obvious leaks which is baffling me! No stains on ceilings or wet floors which I'd expect especially with the frequency of the pressure dropping. Had the heating engineer out (again) and he tells us we'll need a new boiler but I'm not convinced as it works fine when topped up. I've googled and read suggestions about having the system flushed and a new PCV (perhaps wrong letters) unit fitted - none of which the engineer has suggested. Has anyone else had this problem? And is it definitely due to a leak somewhere?
Any suggestions gratefully welcomed
I posted on here a few months ago regarding a different problem with my Ideal Logic 30 boiler and a very kind person helped with their suggestion so I'm hoping for the same again please! Since just before Christmas the boiler keeps losing water pressure, initially with weeks in between however now it requires the pressure increasing a few times per week, as it literally drops completely leaving us without heating or hot water. There are no obvious leaks which is baffling me! No stains on ceilings or wet floors which I'd expect especially with the frequency of the pressure dropping. Had the heating engineer out (again) and he tells us we'll need a new boiler but I'm not convinced as it works fine when topped up. I've googled and read suggestions about having the system flushed and a new PCV (perhaps wrong letters) unit fitted - none of which the engineer has suggested. Has anyone else had this problem? And is it definitely due to a leak somewhere?
Any suggestions gratefully welcomed
My moms got the same. New in 2015/6 and I had to repressurise it a few times but all of a sudden it needs it every two or three weeks otherwise it goes into error mode.
The plumber came to service it and I told him about the problem, he says he noticed a stain on the outside pipe, something about the PRV valve ( I think). We’re trying to find the warranty docs but we will probably end up paying the plumber to fix it.
The plumber came to service it and I told him about the problem, he says he noticed a stain on the outside pipe, something about the PRV valve ( I think). We’re trying to find the warranty docs but we will probably end up paying the plumber to fix it.
HI
If your losing pressure your losing volume of water. Most likely from the PRV (pressure relief valve). Find the small over flow pipe (it will be copper) outside and put a ballon over it if it collects the water then you know the PRV is passing.
The PRV is a small safety valve that lifts when pressure has built up to much, once lifted they often get a small amount of debris on the seating causing then to leak and drop out pressure slowly. You should also get the expansion vessel checked as if this has lost its charge the this will be the cause of the over pressure.
on the logic sometimes the heat exchanger can leak this is not seen as the water runs down through the sump and out to waste the same route as the condensate.
Good luck and get another plumber yours sounds rubbish
ss
If your losing pressure your losing volume of water. Most likely from the PRV (pressure relief valve). Find the small over flow pipe (it will be copper) outside and put a ballon over it if it collects the water then you know the PRV is passing.
The PRV is a small safety valve that lifts when pressure has built up to much, once lifted they often get a small amount of debris on the seating causing then to leak and drop out pressure slowly. You should also get the expansion vessel checked as if this has lost its charge the this will be the cause of the over pressure.
on the logic sometimes the heat exchanger can leak this is not seen as the water runs down through the sump and out to waste the same route as the condensate.
Good luck and get another plumber yours sounds rubbish

ss
Edited by silversurfer1 on Tuesday 13th February 19:07
Has it got an expansion vessel built in the boiler? Ours does exactly as you've described and it's always due to the pressure vessel being low pressure. Once this is topped up through the schrader valve with a bicycle pump/foot pump then all is well again.
I've had engineers tell me that it isn't possible to cause the symptoms but this is how it's been resolved twice now.
As to why the vessel loses pressure is another mystery but when it's such a simple fix, why worry about it.
I've had engineers tell me that it isn't possible to cause the symptoms but this is how it's been resolved twice now.
As to why the vessel loses pressure is another mystery but when it's such a simple fix, why worry about it.
Easiest check is the condensate pipe as above.
If you do get water out of this then it could be the PRV (pressure relief valve). They can get a buildup of crud in the internal seal and this means the valve does not shut properly. Good news is that they can generally be taken apart and cleaned by anyone competent at a bit of DIY.
Check the condensate pipe (some people call it an overflow pipe) and post back. Someone will help you.
If you do get water out of this then it could be the PRV (pressure relief valve). They can get a buildup of crud in the internal seal and this means the valve does not shut properly. Good news is that they can generally be taken apart and cleaned by anyone competent at a bit of DIY.
Check the condensate pipe (some people call it an overflow pipe) and post back. Someone will help you.
Ricky146a said:
Easiest check is the condensate pipe as above.
If you do get water out of this then it could be the PRV (pressure relief valve). They can get a buildup of crud in the internal seal and this means the valve does not shut properly. Good news is that they can generally be taken apart and cleaned by anyone competent at a bit of DIY.
Check the condensate pipe (some people call it an overflow pipe) and post back. Someone will help you.
Is this correct, are the condensate and pressure overflow the same pipe? I've got separate outlets.If you do get water out of this then it could be the PRV (pressure relief valve). They can get a buildup of crud in the internal seal and this means the valve does not shut properly. Good news is that they can generally be taken apart and cleaned by anyone competent at a bit of DIY.
Check the condensate pipe (some people call it an overflow pipe) and post back. Someone will help you.
Hi,
Thank you to all who have taken the time to reply. Since my post yesterday I returned this morning from a night shift to find the boiler is again showing error code F1 however the water pressure gauge is where it should be (so possible error as error code doesn't correlate to the fault) so we now have hot water bottles and blankets to keep us warm this evening. Spoke to plumber who advised checking the copper pipe outside to see if water is coming out but too dark to see. Will keep you posted
Thank you to all who have taken the time to reply. Since my post yesterday I returned this morning from a night shift to find the boiler is again showing error code F1 however the water pressure gauge is where it should be (so possible error as error code doesn't correlate to the fault) so we now have hot water bottles and blankets to keep us warm this evening. Spoke to plumber who advised checking the copper pipe outside to see if water is coming out but too dark to see. Will keep you posted
Paul Drawmer said:
Is this correct, are the condensate and pressure overflow the same pipe? I've got separate outlets.
Oops. Brainfade.You are correct. I checked mine and copper condensate pipe exits the wall right beside my plastic pressure relief pipe.
So I guess, check both pipes and this should help to isolate or eliminate those faults.