Boiler Not Firing for Upstairs Bathroom
Boiler Not Firing for Upstairs Bathroom
Author
Discussion

340600

Original Poster:

611 posts

174 months

Friday 29th May 2020
quotequote all
Morning all,

The water flow/pressure to our upstairs bathroom has been poor since we moved in over a year ago but we were able to get enough hot water for a 5 minute shower - this has since deteriorated to 30 seconds max before the water turns stone cold. The hot and cold flow from the basin is also very poor (as in 30 seconds to fill a pint glass, and limited to no hot water).

Standing next to the boiler while the shower or upstairs hot tap is running and it's silent, turn on any hot taps downstairs and it kicks into life straight away. Also the shower does seem better when the heating has been on, this might be my imagination though.

Severn Trent have measured the flow at the outside tap as 2.8 bar and 18lpm which is within their tolerances.

Local plumbing company shrugged and wanted £470 to "investigate" the problem (this was pre-COVID). Lots of Googling suggests it could be a broken actuator in the boiler, or simply because the flow is so poor upstairs? It is a Worcester Greenstar 30si - again Google suggests that this isn't the ideal boiler for a large Edwardian 4-bed semi with two bathrooms.

I'm becoming more and more frustrated with this and don't have the money to throw at it in the hope of finding the issue - any suggestions would be much appreciated.

Lincsls1

4,109 posts

171 months

Friday 29th May 2020
quotequote all
Morning.
If you have got very poor pressure at the cold taps upstairs, it stands to reason that the hot tap pressure is going to be equally poor, even more so with the resistance of the boiler in circuit.
If the boiler isn't detecting an 'adequate' flow, it won't fire up, that is normal and not a fault. 30 seconds to fill a pint glass from either hot or cold tap is not adequate. I would say, based on this information, the boiler is not the issue, even more so because you state downstairs works just fine.
You might have been getting 'some' hot water if the 'pre-heat' or 'comfort' function is on because the boiler will try and maintain its tiny integral store and the hot tap running upstairs will deplete this even though the flow isn't actually enough to fire the boiler properly.
Why did Severn Trent not check the flow rate upstairs?
Causes for poor pressure are usually due to restriction. This can simply be the amount of pipework, elbows, fittings and routing required to reach the target, and obviously in large old properties this can be exaggerated.

340600

Original Poster:

611 posts

174 months

Friday 29th May 2020
quotequote all
Thanks for the reply - that makes sense. ST's response was basically "not our problem". They test up to the property boundary and that's it.

In that case it sounds like a decent plumber who is able to test for internal pipe issues/blockages is the way forward?

Lincsls1

4,109 posts

171 months

Friday 29th May 2020
quotequote all
As for suggestions and I'm sorry they are crap ones...

Try trace as much of the water pipework as possible and visually inspect it for obvious problems such as kinking.
Any inline isolation valves that you find, make sure they are open fully. For example at my house the cold water feed going upstairs has a gate valve fitted passing through my airing cupboard and if that was partly closed would cause problems.
Check any flexible braided type hoses usually under the basin possible even in the shower pipework aren't stressed or kinked. The internal bore on these is much narrower than a normal 15mm pipe and although facilitate easy installation, they cause a pressure drop.
Eliminate the boiler to settle your mind. Use the downstairs taps, run the hot water and check the boiler runs continuously when the hot tap is flowing well, the flame should not shut off if the flow is good.
Then slow the tap to a reasonably slow flow rate (not too slow though remember) and check the boiler still runs and delivers continuous hot water. The boiler will modulate, slow down, but the hot water should be continuous.
If this is ok, you've eliminated the boiler. Its a start!


Ransoman

884 posts

121 months

Friday 29th May 2020
quotequote all
I may have missed this but what is the flow like downstairs? How long does it take you to fill a Litre jug compared to upstairs?

As a workaround you could try leaving a hot tap on downstairs while running the upstairs tank, assuming that doesn't leave it with no pressure to get upstaires. That will keep the flow up through the boiler.

TwistingMyMelon

6,519 posts

236 months

Friday 29th May 2020
quotequote all
I have similiar in my house

Im guessing its a combi? Whats the pressure like? When mine needs topping up and is in red, it kicks in less easily, I could be imagining it , but topping it up to the green zone seems to help

As others have said you could have crap hoses and taps, mine are all about 10 years old, in a hard water area. Modern taps seem to be designed to use less water so have less flow that exacerbates it

A decent old school plumber should be able to rule out basics quickly, id start with hoses and taps tbh


340600

Original Poster:

611 posts

174 months

Friday 29th May 2020
quotequote all
It is a combi boiler. I try and keep the pressure in the middle of the green zone; I can't say I've noticed any difference when it's higher or lower though.

The pressure downstairs is best described as "adequate". Around 11 seconds to fill a litre jug. Leaving a hot tap running downstairs had crossed my mind but I expected the shower to become unusable - however it turns out to be the opposite, so that's a workaround for the time being.

I have basic HomeServe insurance for 50p a month which covers blockages to sinks, so I've paid a £30 excess and booked a plumbing visit on Monday. I'm not holding out much hope but it may at least help with the diagnosis.

Lincsls1

4,109 posts

171 months

Friday 29th May 2020
quotequote all
340600 said:
It is a combi boiler. I try and keep the pressure in the middle of the green zone as much as possible; I can't say I've noticed any difference when it's higher or lower though.

The pressure downstairs is best described as "adequate". Around 11 seconds to fill a litre jug. Leaving a hot tap running downstairs had crossed my mind but I expected the shower to become unusable - however it turns out to be the opposite, so that's a workaround for the time being.

I have basic HomeServe insurance for 50p a month which covers blockages to sinks, so I've paid a £30 excess and booked a plumbing visit on Monday. I'm not holding out much hope but it may at least help with the diagnosis.
That's right, the boilers 'system' pressure will make no difference to the flow through the taps at all.
Your flow rate downstairs is similar to mine (assuming HW tap). More than adequate to make a combi run, but still crap in all fairness. If your upstairs is much worse, that's why your combi doesn't like it and is not at fault.

Edited by Lincsls1 on Friday 29th May 12:48

IJWS15

2,254 posts

116 months

Friday 29th May 2020
quotequote all
It is summer and water pressure can be lower as lots of people water their gardens.

Many years ago we lived in ST area and some days the water pressure wouldn’t fill the toilet cistern upstairs. ST initially didn’t want to know but eventually the hundreds of complaints from the area resulted in a fix.

It is nothing to do with the pressure shown on the boiler, if that pressure is too low the the boiler will not run period, it is cold water pressure that is the issue.

Have you checked for kinked pipes, small bore pipes etc. in the run to that shower?

It sounds very much that the house isn’t suitable for a combi, had 2 and wouldn’t have another.

Lincsls1

4,109 posts

171 months

Friday 29th May 2020
quotequote all
Taken from a Worcester bulletin....

"The flow rate required to initiate a hot water demand on a Greenstar boiler varies across the range of appliances between 2 & 3 l/min. The boilers will typically end a hot water demand at approximately 1 l/min below the rate at which they started the demand."

Your downstairs flow rate is only just over 5 litres/minute, like mine crap. Bet your upstairs is right on the cusp of switch on, then within seconds it drops below the threshold and switches off. Remember the static/standing pressure will be higher.
Wonder if your main stop tap is ok?scratchchin
Keep us posted on your findings smile

Matt_E_Mulsion

1,746 posts

96 months

Friday 29th May 2020
quotequote all
I'm no expert, but if both the hot and cold upstairs have poor flow rates then it is unlikely to be anything to do with the boiler.

The cold water feed that ends up at the tap upstairs should be fed (more or less) directly from the stop tap.

It sounds like a generic not enough flow/pressure problem through the entire system with the distance to the upstairs taps/shower just exaggerating the problem.

Like another poster said, the first thing to check is that your stop cock/s are turned all of the way on.

340600

Original Poster:

611 posts

174 months

Friday 29th May 2020
quotequote all
Thanks for all the suggestions so far. I neglected to mention that we were relieved of over £100 for a new stop tap some months ago "just in case".

I suspect that Lincs is right and the pressure isn't enough to trigger the boiler's hot water switch (which may well be unsuitable in itself, we've discovered that the previous owner was tighter than a duck's ), the question is why. I'll do a bit more digging and update the thread following Monday's visit.

340600

Original Poster:

611 posts

174 months

Monday 1st June 2020
quotequote all
An update to this: We now have perfectly functioning taps in the bathroom. It was, somewhat embarrassingly, a lot simpler than I thought. There was a load of grit caught in the filter, and "a lot of air" in the system, according to the plumber. It took him all of 15 minutes to fix. Both houses either side of us have been renovated recently, meaning the stop-tap in the road has been turned on and off a few times, he suspects this was the cause.

Next job is to dismantle the shower as it'll almost certainly be the same thing. If anyone knows how to easily access the filter/cartridge in one of these showers I'd be most grateful. hehe