If I have put this in the wrong place please move it to the correct spot
I would like to fit a bollard in the middle of my drive as added protection
The one I like in the details says Breaking resistance: 110,000J
Could someone please put this into terms I can understand? ie a VW polo hitting it at 10 MPH or a 7.5 tonne truck hitting it at 30 MPH I have asked the supplier but they just said there are a lot of different things that would affect its impact.
If the bollard will not stop a slow moving car it is not what i want
Thanks for looking

Jimbo.

4,231 posts

219 months

Wednesday 17th May 2023
quotequote all
6 pot said:
If I have put this in the wrong place please move it to the correct spot
I would like to fit a bollard in the middle of my drive as added protection
The one I like in the details says Breaking resistance: 110,000J
Could someone please put this into terms I can understand? ie a VW polo hitting it at 10 MPH or a 7.5 tonne truck hitting it at 30 MPH I have asked the supplier but they just said there are a lot of different things that would affect its impact.
If the bollard will not stop a slow moving car it is not what i want
Thanks for looking
A 1500Kg car moving at 10mph has approx. 15000J of kinetic energy.

6 pot

Original Poster:

58 posts

214 months

Wednesday 17th May 2023
quotequote all
Thanks so 110000j should be enough ram raid protection
I will get it fitted

Grrbang

755 posts

101 months

Wednesday 17th May 2023
quotequote all
Kinetic energy (Joules) is 1/2 x mass (kg) x velocity^2 (m/s).

110,000J is 13.5m/s for a 1200kg vehicle, or 30mph.

For a 7500kg vehicle, it would be 12mph.

While it is easy to design a steel column with enough strength to completely destroy a car, providing sufficient foundations is another matter.

Breaking resistance isn’t a normal engineering term unless there is a standard defining it. Joules also aren’t a standard unit for defining strength. I suspect they presented as 110,000J because big numbers must be good!

I suspect the number is meaningless except for comparative purposes. If I were buying a bollard, I would consider it a deterrent and nothing more. Convenience features such as remote retraction would be of more interest.

PurpleFox

507 posts

115 months

Thursday 18th May 2023
quotequote all
From the above calculations, it would seem a fairly substantial bollard - but what are you fixing it to and how are you fixing it? Surely that is going to be the weakest point (by far).

A bollard to stop a car at 30mph would have to be buried quite deep into the ground.

cml24

1,587 posts

177 months

Thursday 18th May 2023
quotequote all
PurpleFox said:
From the above calculations, it would seem a fairly substantial bollard - but what are you fixing it to and how are you fixing it? Surely that is going to be the weakest point (by far).

A bollard to stop a car at 30mph would have to be buried quite deep into the ground.
I have the results on some tests we had done at work. They used an armoured personal carrier to hit the bollards. Some of the bollards have a foundation that is 1.4m x 1.4m by 1m deep. Thats only for a 90mm diameter bollard. I would agree that the fixing/foundation is likely to be the weak point.