Help with 13a Fused Spur box
Help with 13a Fused Spur box
Author
Discussion

eltax91

Original Poster:

10,394 posts

223 months

Yesterday (12:08)
quotequote all
Hi all

I am doing some modification to my garage and I have made a small board with some sockets and a VFD on, fed from a live from the consumer unit.

In my VFD thread, somebody suggested I use an isolator before the board so I could switch off the entire input which made sense. So I bought a brand new one of these:



I fitted this. With the inbound wires from the circuit board on the supply poles and the wires to my socket on the ‘load’ poles.

Thing is. It doesn’t work. Doesn’t pass current. Diagnosis with multimeter:

1. Switch OFF no continuity between L supply and L load. No continuity between N supply and N load

2. Switch ON successful continuity between L supply and L load. NO continuity between N supply and N load.

The fuse inside has continuity end to end. I have fitted a wago connector to join the wires for now and that works. Socket and VFD both power up.

So…. Is this suitable for the job of isolating a double socket and a VFD? Did I blow it up myself? Or did I just get unlucky and Amazon sent me a duff?

OutInTheShed

12,044 posts

43 months

Yesterday (13:09)
quotequote all
Seems to be dead!

Rough101

2,754 posts

92 months

Yesterday (13:30)
quotequote all
Get a replacement, from a better brand.

This sort of thing never used to happen, common now.

119

13,838 posts

53 months

Yesterday (13:51)
quotequote all
I tried to fit one of these once and called a sparky to look at it.

Turns out I pushed the cable too far in to the terminal and did the screw up on the sleeving rather than the bare wire.


Gladers01

1,369 posts

65 months

Yesterday (14:08)
quotequote all
Rough101 said:
Get a replacement, from a better brand.

This sort of thing never used to happen, common now.
Common or Neutral seems to be the problem, pop the facing plate off so at least we can see the terminals and do a post mortem smile

eltax91

Original Poster:

10,394 posts

223 months

Yesterday (15:52)
quotequote all
Gladers01 said:
Common or Neutral seems to be the problem, pop the facing plate off so at least we can see the terminals and do a post mortem smile
Never even thought about that. Here’s the mess within as I lifted the plate




Gladers01

1,369 posts

65 months

Yesterday (17:23)
quotequote all
eltax91 said:
Never even thought about that. Here s the mess within as I lifted the plate



Gosh, that looks a right mess, return it to Amazon asap as not fit for purpose yikes

eltax91

Original Poster:

10,394 posts

223 months

Yesterday (18:25)
quotequote all
Gladers01 said:
Gosh, that looks a right mess, return it to Amazon asap as not fit for purpose yikes
Already pressed the buttons. They don’t want it back, as I opted for credit to balance. So it’s in the bin and I’ll be off to CEF tmr