Boiler requirements for a 5 bedroom, 5 bathroom house
Boiler requirements for a 5 bedroom, 5 bathroom house
Author
Discussion

Returningmember

Original Poster:

70 posts

85 months

Evening.
I'm having a new house built and have had two very different opinions on the boiler requirement to sufficiently run the heating and hot water.

Gas engineer 1 says I will need 2 boilers and a cylinder in a dedicated plant room. One boiler to run 8 radiators underfloor heating, and two bathrooms, and a second boiler to run 12 radiators and three bathrooms.

Gas engineer 2 said a large combi or system boiler with a cylinder would be enough for the entire house.

I had a new 25mm water main put in, and the plumber has already installed a 22mm pipe the length of the house with 22mm runs to the rads, switching to 15mm no more than 500mm from each rad.

2 parents and 2 kids so realistically 3 showers at any one time, possibly 4 maximum. Not really fussed about zoning the upstairs and downstairs rads.

I get that different engineers will have different preferences, but it seems they're at each end of the spectrum.

Does anyone have similar setups, or any tips/pitfalls to avoid?

TIA

Nothingtoseehere

4,810 posts

208 months

3,000 square ft, 18 rads, 5 bathrooms- 1 boiler and a large cylinder works for us.

If I was building I'd be considering an ASHP, but that's not what you asked

Returningmember

Original Poster:

70 posts

85 months

Nothingtoseehere said:
3,000 square ft, 18 rads, 5 bathrooms- 1 boiler and a large cylinder works for us.

If I was building I'd be considering an ASHP, but that's not what you asked
Thank you smile

sherman

14,778 posts

236 months

I would go with option 1 if space and finnances allow
2 smaller boilers are going to be under alot less stress and cheaper to run than a big beast to power everything on its own.

Make sure the hot water tank has an emmersion heater as a redundancy. Just in case the heating goes.
I would also make the shower in the spare bedroom an electric shower so if your hot water goes you can still have a shower.





dobly

1,529 posts

180 months

To do it right, more info is required..
Where is the house? Up a mountain in Northern Scotland or on the South Coast neat Torquay?
What s the floor area? What ceiling heights? Double or triple glazing? What insulation has been used? To code or way above? What distances from one end of the house to another?
Just supplying bedroom and bathroom numbers without context isn t going to design the right system for the house.
It all depends on the individual project - what works in one place might not be as good in another 5bed, 5bath property.
Ask both why their approach is better than what the other has suggested - that should be telling.

Edited by dobly on Monday 12th January 20:51

Crumpet

4,902 posts

201 months

I am absolutely not saying that this is the way to go, but we run a 3000 sq ft, 200 year old house with five beds and three baths off a 28kw combi with 20 rads. It’s absolutely fine and even runs two showers at once.

I am by no means an expert, but 3000 sq ft isn’t a big house, so a single system boiler and big cylinder sounds more than adequate.

Nothingtoseehere

4,810 posts

208 months

Crumpet said:
I am absolutely not saying that this is the way to go, but we run a 3000 sq ft, 200 year old house with five beds and three baths off a 28kw combi with 20 rads. It s absolutely fine and even runs two showers at once.

I am by no means an expert, but 3000 sq ft isn t a big house, so a single system boiler and big cylinder sounds more than adequate.
The house size was mine rather then the OPs, but sounds similar on the beds/baths so shared my experience.

fooman

974 posts

85 months

Crumpet said:
I am absolutely not saying that this is the way to go, but we run a 3000 sq ft, 200 year old house with five beds and three baths off a 28kw combi with 20 rads. It s absolutely fine and even runs two showers at once.

I am by no means an expert, but 3000 sq ft isn t a big house, so a single system boiler and big cylinder sounds more than adequate.
Half the size but 11 rads on 28kw combi which was fitted when we were 2 beds now 4 we thought it may struggle but been fine for a decade. Only just runs 2 showers though.

Crumpet

4,902 posts

201 months

Nothingtoseehere said:
The house size was mine rather then the OPs, but sounds similar on the beds/baths so shared my experience.
Ah. Sorry. Skim reading!

Jeremy-75qq8

1,593 posts

113 months

If it is a new build ( assuming you are on the uk ) then it will be built to the new regs that came in about 2 years ago.

We have a large house completed in 2023 to the old regs.

It simply does not get cold. The whole house is heated by the hall / kitchen / my office that is it. It is 3 floors. The house is about 21 degrees all over.

We have under floor heating. We have one boiler.

Your contractor will have to have sap calculations to pass regs a that will give energy requirement.

It won't be much.

Andeh1

7,452 posts

227 months

A house that size to latest regulations does not require two boilers.... rofl

I've got a similar size place, with less insulation and a very inefficient design, and an 8kw ASHP that works perfectly well, & even during cold spells only runs part time.

No idea what the equivalent is for gas boiler, but it won't be overly big.... 30kw ish, at a guess?! Then get a 300L cylinder, that'd do 4 easy showers, 2 running at the same time.

I don't see how your water pressure can run 3 showers at the same time, let alone boilers to keep up?

Edited by Andeh1 on Monday 12th January 21:46

8-P

3,114 posts

281 months

5 beds,3 bathrooms, 17 ish rads I think. Just had a new 35kw boiler installed and have a 200L megaflo, I have hot water timed around showers so we never run out. I think you’ll be fine.

DonkeyApple

65,698 posts

190 months

Returningmember said:
Evening.
I'm having a new house built and have had two very different opinions on the boiler requirement to sufficiently run the heating and hot water.

Gas engineer 1 says I will need 2 boilers and a cylinder in a dedicated plant room. One boiler to run 8 radiators underfloor heating, and two bathrooms, and a second boiler to run 12 radiators and three bathrooms.

Gas engineer 2 said a large combi or system boiler with a cylinder would be enough for the entire house.

I had a new 25mm water main put in, and the plumber has already installed a 22mm pipe the length of the house with 22mm runs to the rads, switching to 15mm no more than 500mm from each rad.

2 parents and 2 kids so realistically 3 showers at any one time, possibly 4 maximum. Not really fussed about zoning the upstairs and downstairs rads.

I get that different engineers will have different preferences, but it seems they're at each end of the spectrum.

Does anyone have similar setups, or any tips/pitfalls to avoid?

TIA
The second plumber appears to use less gack at breakfast.

Current house is a leaky old, single glazed 2500 with 15 or so rads. It runs perfectly well on a boggo combi. Previous one was leaky, 5000 sqft with 30 or so rads and just used a normal boiler and a mega flow tank.

PhilboSE

5,642 posts

247 months

A 30kW or 36kW boiler on its own should be plenty. If you really want to run 3 showers at once then you absolutely need a HW cylinder and an accumulator in front of that. As a new build you might want to consider solar thermal heating for the tank(s) as well.

There’s no way you need 2 boilers for that. It adds more complexity to the system than you might think and you would usually have bigger primaries even than the 22mm pipes you have.

mikeiow

7,610 posts

151 months

I’d have wet underfloor heating as a preference to rads, at least on the ground floor, for starters.
More wall space for flexibility, & a comfortable experience (purely based on our sun room extension we had done a decade ago).

A single boiler should be fine: ours is a system boiler, which makes for a decent power shower. Currently feeds 19 rads and wet UFH in a 40m2 sunroom.
That said, if all 3 showers were in use at once, pressure might drop a bit…..& the idea of an electric spare is a good one.

ASHP? Perhaps, with a decent battery system to backup (& obvs solar). No personal experience, although with a modern well insulated house, it could work….although my only experience with electric UFH was some we retrofitted which was HUGELY expensive eek


okgo

41,279 posts

219 months

11 rads here, 3 bathrooms, we have a 30kw boiler and cylinder. It’s fine.

Hobo

6,274 posts

267 months

Yesterday (06:18)
quotequote all
4500sqft house (over 4 1/2 floor), 25 radiators, 4 bathrooms.

1 boiler and 1 cylinder. No issues.

There is definitely no need for OP to be installing 2 boilers, although if space and finances suit then it’s certainly something worth considering as will mean the equipment is less stressed and in the event of a boiler failure you’ll have a backup.

Jonathan27

750 posts

185 months

Yesterday (06:47)
quotequote all
We have seven beds and six bathrooms. All heated from one boiler, we had it replaced a few months back and they fitter a 32Kw, and its absolutely fine. But a large water tank is essential, and we have also seen the benefit of using solar to heat water also.

Murph7355

40,803 posts

277 months

Yesterday (07:35)
quotequote all
Similar to others who've posted... 3k sqft, 7beds, 4baths...leaky old place.

Std system boiler and h/w tank. Get a decent sized tank and it'll be fine.

Unless space was at a premium I'd never have a comb.

I'd go ASHP only if the house could be well insulated and had solar PV.

B5mike

510 posts

170 months

Yesterday (08:12)
quotequote all
Over 5,000 sq ft here, very old house with 5 bathrooms all off one oil boiler and a single hot water cylinder. Currently getting a heat loss survey done and early indications are that the boiler (70kW) is way oversized.
In my experience gas/oil engineers don't do maths, they just oversize and over complicate stuff to make sure they never undersize, without knowing what is actually needed.
For a new build I'd definitely be going ASHP.