UFH Issues - hydraulic balancing problem
UFH Issues - hydraulic balancing problem
Author
Discussion

Too Late

Original Poster:

5,158 posts

266 months

I'm having an issue with the underfloor heating in my house and wondered what the world of PH thinkgs

System setup:
Vaillant ecoTEC plus 630 system boiler.
Three underfloor heating manifolds: two upstairs (located together) and one downstairs.
Each manifold has its own circulation pump and motorised zone valve.
Heating is controlled through Loxone, which opens the relevant zone valve and starts the manifold pump when heat is requested.
The primary heating flow and return appear to be 22 mm copper throughout.
The pipework runs from the boiler into the ceiling between the ground and first floors, feeding the two upstairs manifolds before continuing to the downstairs manifold via tees.

The problem:
Each manifold works correctly when operated independently.
Downstairs only: heats correctly.
Upstairs only: heats correctly.
Upstairs and downstairs together: upstairs heats normally, but downstairs stops receiving sufficient hot water and goes cold.
The motorised valves appear to open correctly and the circulation pumps start as expected.

When the problem occurs, the downstairs manifold's temperature gauge reads approximately 25°C, despite its thermostatic mixing valve being set to around 45°C. The primary pipe on the return side also feels hotter than the pipe feeding the mixing valve.

Chat GPT suggests a possible issue as a hydraulic balancing problem, with the upstairs manifolds receiving most of the available flow when multiple zones operate.

This doesnt sounds like a simple fix.

Pumber mentioned having to get a system designed so it includes a low loss header as flows need to be measured.....

Anyone had experience with this before?

Thanks

silversurfer1

940 posts

167 months



Difficult to say but before you invest in a low loss header, check the flow rates out to each individual loop they can be set on the flow limiters and should be set as per the UFH design. importantly have the UFH pumps set on the lowest setting you can get away with to achieve the litres per minute required per circuit.

Check you don't have any bypasses on the ufh manifold that are fully open

If you have any flow and return valves to the manifolds try cranking the flow down on the one that is working well to balance it to the others.

Check the software settings on the 630 so pump output is at maximum

The ufh pumps are solely for pushing the water around the underfloor heating circuits they have no bearing and shouldn't be relied on to get the water from the boiler to the manifolds,

Most importantly make sure they have the Flow and Return pipe work correctly connected to the manifold and that the Manifold pump is pumping in the correct direction, quick look at the manufactures instructions will make this clear, ive come across a few that are incorrectly piped because the flow often looks like it goes into the return of the manifold, this is because the manifold is mixing the water before it sends it out to the floors.


good luck

ss


Too Late

Original Poster:

5,158 posts

266 months

silversurfer1 said:
Difficult to say but before you invest in a low loss header, check the flow rates out to each individual loop they can be set on the flow limiters and should be set as per the UFH design. importantly have the UFH pumps set on the lowest setting you can get away with to achieve the litres per minute required per circuit.

Check you don't have any bypasses on the ufh manifold that are fully open

If you have any flow and return valves to the manifolds try cranking the flow down on the one that is working well to balance it to the others.

Check the software settings on the 630 so pump output is at maximum

The ufh pumps are solely for pushing the water around the underfloor heating circuits they have no bearing and shouldn't be relied on to get the water from the boiler to the manifolds,

Most importantly make sure they have the Flow and Return pipe work correctly connected to the manifold and that the Manifold pump is pumping in the correct direction, quick look at the manufactures instructions will make this clear, ive come across a few that are incorrectly piped because the flow often looks like it goes into the return of the manifold, this is because the manifold is mixing the water before it sends it out to the floors.


good luck

ss
Thanks very much for the reply... I will thorugh the list of pointers. Thanks again

HarryW

16,096 posts

300 months

Know zero about UFH but the use of a 3rd party control system, Loxone in this case (substitute Hive in other applications), means the actual Boiler is never going to be used efficiently as the loxone will just send a simple 230v on/off signal to the boiler.
Any reason you didn’t go with proprietary Vaillant SensoComfort based system?