Combi boiler not producing hot enough water ?
Combi boiler not producing hot enough water ?
Author
Discussion

Merlot

Original Poster:

4,121 posts

239 months

Monday 15th February 2010
quotequote all
I am new to Combi boilers, having lived for years with a hot-water tank setup.

When I run a bath, the hot water seems to come out of the tap about 65-70c, which is what the boiler indicates on it's control panel.

Having grown up with super hot baths which come close to scalding you, I am finding recent baths a bit too cool. Is this a normal occourance with a combi boiler or should it produce hotter water?

B17NNS

18,506 posts

278 months

Monday 15th February 2010
quotequote all
Turn down the bath tap a bit (ie reduce the flow) and see if that helps.

The water will move through the boiler slower and should get hotter.

Also check on the boiler that the hot water circuit is set to its maximum.

Big Al.

69,336 posts

289 months

Monday 15th February 2010
quotequote all
I've found that if you have the heating on as well the water temperature will suffer if you have the tap on full bore. Either turn off the heating until you've run the bath or turn down the tap and run the bath slower. smile

Merlot

Original Poster:

4,121 posts

239 months

Monday 15th February 2010
quotequote all
I'll try turning the tap down a bit next time.

Mind you, this raises another issue: It seems to take forever to fill the bath as it is. It was the same when we were in our last place (which also had a Combi boiler and suffered from cool bath syndrome).

With the hot water tank system, I could fill the bath in about 3 mins max. Now it is closer to 10. I hate to think how long it'll be with the taps turned down! biggrin

eldar

25,368 posts

227 months

Monday 15th February 2010
quotequote all
Its winter, so in inlet water is cold, so needs lots of energy, pushing the boiler to maximum.

It will be OK in summer.

Ferg

15,242 posts

288 months

Monday 15th February 2010
quotequote all
Merlot said:
I'll try turning the tap down a bit next time.

Mind you, this raises another issue: It seems to take forever to fill the bath as it is. It was the same when we were in our last place (which also had a Combi boiler and suffered from cool bath syndrome).

With the hot water tank system, I could fill the bath in about 3 mins max. Now it is closer to 10. I hate to think how long it'll be with the taps turned down! biggrin
Welcome to the wonderful world of the Combination Boiler......

V8mate

45,899 posts

220 months

Monday 15th February 2010
quotequote all
You run a bath at 65-70C? And add no cold?

That can't be good for you.

My combi is set at 55C!

Guffy

2,372 posts

296 months

Monday 15th February 2010
quotequote all
Ferg said:
Merlot said:
I'll try turning the tap down a bit next time.

Mind you, this raises another issue: It seems to take forever to fill the bath as it is. It was the same when we were in our last place (which also had a Combi boiler and suffered from cool bath syndrome).

With the hot water tank system, I could fill the bath in about 3 mins max. Now it is closer to 10. I hate to think how long it'll be with the taps turned down! biggrin
Welcome to the wonderful world of the Combination Boiler......
But if you only use the shower and live by yourself (me!), then they can make sense.

Simpo Two

93,127 posts

296 months

Monday 15th February 2010
quotequote all
Actually you could fill a bath with cold water and bubble superheated steam through it...



Better still, bubble your buns this winter with the new Simpo (TM) Induction Bath: all you need is steel bath, two induction hobs strapped to each side and a 3-phase supply biggrin

sjj84

2,396 posts

250 months

Monday 15th February 2010
quotequote all
Is it a new boiler? Do you get a lot of limescale in your water? My bath was taking ages to fill, getting worse over time, had the boiler descaled and it's made the world of difference.

Ricky_M

6,618 posts

250 months

Monday 15th February 2010
quotequote all
Seriously doubt the Domestic Hot Water is coming out as 65c. Thats most probably the temp of the water in the heating system.

Could be a number of things causing the water to be cool. Flow switch, thermistors, gas valve, diverter valve, blocked plate heat exchanger etc.....

Most combination boilers only raise the inlet temp by around 35c, so if your incoming mains temp is 5c, your not going to get scalding water. Try throttling back the cold water isolation valve on the boiler to reduce the flow rate.

What boiler is it?

telecat

8,528 posts

272 months

Tuesday 16th February 2010
quotequote all
What is your boiler rated at? Mine is a bit under powered for our house so that showers tend to be a bit cool. However the baths tend to be ok.

dirkgently

2,160 posts

262 months

Tuesday 16th February 2010
quotequote all
telecat said:
What is your boiler rated at? Mine is a bit under powered for our house so that showers tend to be a bit cool. However the baths tend to be ok.
How dose that work then? Your shower must be like Niagara falls.

telecat

8,528 posts

272 months

Tuesday 16th February 2010
quotequote all
dirkgently said:
telecat said:
What is your boiler rated at? Mine is a bit under powered for our house so that showers tend to be a bit cool. However the baths tend to be ok.
How dose that work then? Your shower must be like Niagara falls.
On a cold morning the effort of running 8 radiators and the shower is a bit much for a 28KW Boiler luckily it's a Worcester so it copes but we should have got the 42KW.

dirkgently

2,160 posts

262 months

Tuesday 16th February 2010
quotequote all
telecat said:
dirkgently said:
telecat said:
What is your boiler rated at? Mine is a bit under powered for our house so that showers tend to be a bit cool. However the baths tend to be ok.
How dose that work then? Your shower must be like Niagara falls.
On a cold morning the effort of running 8 radiators and the shower is a bit much for a 28KW Boiler luckily it's a Worcester so it copes but we should have got the 42KW.
A combi boiler dosent try to heat water and run the central-heating at the same time,it switches between the two with priority given to the hot water. a 28kW boiler should give a delta T of 30 degrees C at 12lpm if you require a 42kW combi you need to rethink the system imo

telecat

8,528 posts

272 months

Tuesday 16th February 2010
quotequote all
dirkgently said:
telecat said:
dirkgently said:
telecat said:
What is your boiler rated at? Mine is a bit under powered for our house so that showers tend to be a bit cool. However the baths tend to be ok.
How dose that work then? Your shower must be like Niagara falls.
On a cold morning the effort of running 8 radiators and the shower is a bit much for a 28KW Boiler luckily it's a Worcester so it copes but we should have got the 42KW.
A combi boiler dosent try to heat water and run the central-heating at the same time,it switches between the two with priority given to the hot water. a 28kW boiler should give a delta T of 30 degrees C at 12lpm if you require a 42kW combi you need to rethink the system imo
The system is balancing quite well at the moment but when I went on the Worcester site and inputed the number of Bedrooms and Bathrooms we have it comes out saying we need the 42. It definitely does not heat the water up as well in the current weather.

Deva Link

26,934 posts

276 months

Tuesday 16th February 2010
quotequote all
dirkgently said:
A combi boiler dosent try to heat water and run the central-heating at the same time,it switches between the two with priority given to the hot water.
Well, that's the theory but the diverter valve often gives problems and either doesn't switch over fully, or at all.

dirkgently

2,160 posts

262 months

Tuesday 16th February 2010
quotequote all
If you have more than one bathroom a combi probably wasn't the answer and in my experience the 42kW brings its own set of problems.

telecat

8,528 posts

272 months

Tuesday 16th February 2010
quotequote all
dirkgently said:
If you have more than one bathroom a combi probably wasn't the answer and in my experience the 42kW brings its own set of problems.
Please elucidate!!

Cold bathValerie

1 posts

176 months

Friday 16th March 2012
quotequote all
I have a combi boiler anew one
I turned off the central haeting.
I turned the water temp to maximum
I waited ten minutes
I ran the hot tap only
Result 2 1/2 ins of hot water ,then it ran cold !