Please help needed
Discussion
Hi I am new to this I was wondering if any of you could help me I have a four post ramp 3 phase 3 hp and have just moved yard and I am looking for something to help me run it I have normal single phase electric, many people have said I need different things and I am seeking people's advice as to what I need to run it thanks
You are probably getting different advice as there's more than one way to do it. Most supplies are three phase until they hit the meter so you can probably get three phase installed. You can get three phase "convertors" - but that's all I know and have no experience of them. The other possibility is changing the motor(s) to single phase.
None of it's likely to be a cheap fix - it might be cheaper to sell yours and buy a single phase one or do a swap.
None of it's likely to be a cheap fix - it might be cheaper to sell yours and buy a single phase one or do a swap.
V8forweekends said:
You are probably getting different advice as there's more than one way to do it. Most supplies are three phase until they hit the meter so you can probably get three phase installed. You can get three phase "convertors" - but that's all I know and have no experience of them. The other possibility is changing the motor(s) to single phase.
None of it's likely to be a cheap fix - it might be cheaper to sell yours and buy a single phase one or do a swap.
3 phases in the main in the ground. A single phase is taken from one of the three in the main to the meter.None of it's likely to be a cheap fix - it might be cheaper to sell yours and buy a single phase one or do a swap.
I need to know more about your motor, but largely :
If you have a three phase motor that can be wired in star or delta you will currently have it in star, as you've been running it off a three phase 415 supply.
If you change the motor to delta (by adjusting/moving some links), you may run it off a single phase supplied inverter.
It really is as simple as that.
Please please please be careful with advice you receive off here, I have seen some incredible things written.
If you have no other reason to need a three phase supply, an inverter will be by far the cheapest option.
I am an industrial electronics engineer, so ask away, I'm more than happy to help.
Edited to add, please take a good clear picture of the rating plate on your motor, and post it up.
AC motors, which yours will be, can vary, depending upon size, as to what voltages/windings.
For example, and it does vary slightly by make, up to about 4KW they will be 220 delta. 380 star, above 4KW, they tend to be 380 delta, 680 star....... ish !
If you have a three phase motor that can be wired in star or delta you will currently have it in star, as you've been running it off a three phase 415 supply.
If you change the motor to delta (by adjusting/moving some links), you may run it off a single phase supplied inverter.
It really is as simple as that.
Please please please be careful with advice you receive off here, I have seen some incredible things written.
If you have no other reason to need a three phase supply, an inverter will be by far the cheapest option.
I am an industrial electronics engineer, so ask away, I'm more than happy to help.
Edited to add, please take a good clear picture of the rating plate on your motor, and post it up.
AC motors, which yours will be, can vary, depending upon size, as to what voltages/windings.
For example, and it does vary slightly by make, up to about 4KW they will be 220 delta. 380 star, above 4KW, they tend to be 380 delta, 680 star....... ish !
Edited by Nigel Worc's on Thursday 6th March 23:02
Gassing Station | General Gassing | Top of Page | What's New | My Stuff


