So I have a floodlight control unit installed in my house that uses 12v pir detectors to switch 240v 1500w capacity floodlight circuits via a mains relay.

The relay looks like it has a capacitor across the load contacts to prevent arcing on switching a 6A 240v load.

I've changed the floodlight halogen bulbs to 12w led cornbulbs.

When the load relay activates the cornbulbs just flicker on and off rapidly.

I'm pretty sure the relay is staying on, but the output circuit is probably oscillating through the capacitor due to the low current load of the cornbulbs.

What's the best way to stop this without upping the current too much?

So I don't want to use a halogen in 1 floodlight for example.

Tech support suggested placing a relay onto the relay output so the load relay just switches the second mains relay which then switches the low current cornbulbs.

I'm thinking of adding an RC snubber to the original relay but maybe I should just remove the capacitor?


clockworks

7,814 posts

176 months

Thursday 11th June 2015
quotequote all
I would try shorting the relay output first (solder a piece of wire across the switched terminals) to check that all the lights and wiring are OK. If this works, remove the wire and the capacitor, and if the lights then start flickering again, try cleaning the relay contacts, or replacing it with something smaller.

TonyRPH

13,550 posts

199 months

Thursday 11th June 2015
quotequote all
Once activated, the relay would effectively short out the capacitor so the capacitor is unlikely to be causing oscillation.

Unless the relay contacts are badly burned and offering a high series resistance to the load - but then your halogens probably wouldn't have worked properly, if at all.

I would doubt that the PIR unit has any kind of load detection built in, but if it does, this could be the issue.

If the relay was oscillating, you would surely hear it in the form of a buzzing (depending on how fast it's oscillating..).

Placing a second relay to be switched by the first is pointless, as the second relay would draw a similar amount of power (or less) than the cornbulb.

If the relay is working correctly, and being driven correctly, it really shouldn't matter if there is a capacitor across the contacts or not, given the light load you are switching.

However - depending on the value of this capacitor - it may (very big may) be possible for the cornbulb to be lit (and oscillate) when the relay is open.

I would start by disconnecting the capacitor completely and test.


SickAsAParrot

304 posts

143 months

Thursday 11th June 2015
quotequote all
The capacitor probably has a resistor already built into it, I can't see it just being a capacitor on its own. In any case if the relay is shut the snubber doesn't factor into the circuit at all (unless has been suggested the contacts are dirty).

If it's only a 12w load you don't need it anyway, chop it out and see what happens. You sure the bulbs are AC and not DC?

rfisher

Original Poster:

5,069 posts

314 months

Thursday 11th June 2015
quotequote all
Thanks for the suggestions - turns out it was the China factor again.

Bulb was faulty.

I have 5 floodlights and that was the 1st bulb I'd replaced grumpy.

Just tested the other 4 bulbs and they work fine.

So gone from 3kw down to 60w.

Just hope I'm not having to replace these new leds very often.