Why is there a fuse in my loft?
Why is there a fuse in my loft?
Author
Discussion

Puggit

Original Poster:

49,468 posts

272 months

Thursday 1st September 2011
quotequote all
We have an approx 6 year old David Wilson house, up in the loft there is a box with a 13amp fuse in it. One grey flattish cable enters, and I can't see any exit for cabling:



Nearby there is the cabling for the non-installed alarm system.

Any ideas? Is it as obvious as it seems (ie power for alarm)? I can't see how to draw power out of the box though...

Thanks!

Muncher

12,235 posts

273 months

Thursday 1st September 2011
quotequote all
Extractor fan or shower perhaps?

Alfa numeric

3,158 posts

203 months

Thursday 1st September 2011
quotequote all
Could it be a provision for a light up there?

Fer

7,765 posts

304 months

Thursday 1st September 2011
quotequote all
Pull the fuse and see what stops working?

Puggit

Original Poster:

49,468 posts

272 months

Thursday 1st September 2011
quotequote all
It's above our spare room, and a fair distance from the 2 bathrooms. I'm guessing it's for the alarm, but surely that wouldn't need 13amps?

Puggit

Original Poster:

49,468 posts

272 months

Thursday 1st September 2011
quotequote all
Fer said:
Pull the fuse and see what stops working?
Nothing changes. As the cable enters but doesn't leave, I'm assuming nothing is powered through there.

anonymous-user

78 months

Thursday 1st September 2011
quotequote all
Puggit said:
I'm guessing it's for the alarm, but surely that wouldn't need 13amps?
It wouldn't but the box prob. came with one as standard as that is what it will be rated to.

Meeja

8,290 posts

272 months

Thursday 1st September 2011
quotequote all
As has been said, an alarm panel would not need 13A, but the spur unit probably came with a 13A fuse as standard.

Spec is correct for an alarm panel as well (unswitched) and ideally, it should be run from the non-RCD side of a split consumer unit, via it's own RCBO (Thay way if the RCD trips, it will not remove power from the alarm system, and the alarm system is still protected by the RCBO)

Unlikely it has been configured that way though....

Puggit

Original Poster:

49,468 posts

272 months

Thursday 1st September 2011
quotequote all
Meeja said:
As has been said, an alarm panel would not need 13A, but the spur unit probably came with a 13A fuse as standard.

Spec is correct for an alarm panel as well (unswitched) and ideally, it should be run from the non-RCD side of a split consumer unit, via it's own RCBO (Thay way if the RCD trips, it will not remove power from the alarm system, and the alarm system is still protected by the RCBO)

Unlikely it has been configured that way though....
Ha!

Funny you should say that... I've just tried to work out which RCD it is wired through so that I can safely connect something in to the box permanently and I can't find a trippy thing that switches it off. As I'm planning on wiring in external security lights (2x75W) to this box I'm not sure if that's a good thing...

Meeja

8,290 posts

272 months

Thursday 1st September 2011
quotequote all
It is probably spurred off the upstairs ringmain. Is it possible to trace the T&E cable that enters the spur?

Puggit

Original Poster:

49,468 posts

272 months

Thursday 1st September 2011
quotequote all
Meeja said:
It is probably spurred off the upstairs ringmain. Is it possible to trace the T&E cable that enters the spur?
It's all hidden under masses of insulation that I have no desire to move! Tripping the 4 switches for upstairs/downstairs lights and upstairs/downstairs mains didn't cut the power. It did piss my wife off however, as when I warned her to warn our son that his computer was about to go off, she didn't think that applied to her too rolleyes

Meeja

8,290 posts

272 months

Thursday 1st September 2011
quotequote all
Firstly, rofl at the wife!

Sounds a little odd that you can't isolate it... What are you using to test the fuse spur to establish whether it is still live or not?


bimsb6

8,635 posts

245 months

Thursday 1st September 2011
quotequote all
Meeja said:
Firstly, rofl at the wife!

Sounds a little odd that you can't isolate it... What are you using to test the fuse spur to establish whether it is still live or not?
the wife with a wet finger i hope .

hidetheelephants

34,211 posts

217 months

Thursday 1st September 2011
quotequote all
bimsb6 said:
Meeja said:
Firstly, rofl at the wife!

Sounds a little odd that you can't isolate it... What are you using to test the fuse spur to establish whether it is still live or not?
the wife with a wet finger i hope .

Simpo Two

91,607 posts

289 months

Thursday 1st September 2011
quotequote all
What do you intend to do if you ever find out what it was for?

Puggit

Original Poster:

49,468 posts

272 months

Friday 2nd September 2011
quotequote all
I've opened it up, there's an in cable, and connectors for an out. So I'm wiring in a 4 way adaptor and setting up a light in the loft and one outside. This leaves 2 sockets for a train set some day wink

Meeja

8,290 posts

272 months

Friday 2nd September 2011
quotequote all
Puggit said:
I've opened it up, there's an in cable, and connectors for an out. So I'm wiring in a 4 way adaptor and setting up a light in the loft and one outside. This leaves 2 sockets for a train set some day wink
Only viable if the incoming twind and earth is 2.5mm (ie spurred off a ringmain or similar)

If the incoming is 1.5mm (or even 1mm) then it is probably linked to a lighting circuit somewhere, and putting sockets on that you can load up is dodgy ground.

Still haven't established where it comes from though.... Are you in a semi, and it is fed from next door?!

Puggit

Original Poster:

49,468 posts

272 months

Friday 2nd September 2011
quotequote all
Meeja said:
Puggit said:
I've opened it up, there's an in cable, and connectors for an out. So I'm wiring in a 4 way adaptor and setting up a light in the loft and one outside. This leaves 2 sockets for a train set some day wink
Only viable if the incoming twind and earth is 2.5mm (ie spurred off a ringmain or similar)

If the incoming is 1.5mm (or even 1mm) then it is probably linked to a lighting circuit somewhere, and putting sockets on that you can load up is dodgy ground.

Still haven't established where it comes from though.... Are you in a semi, and it is fed from next door?!
Nope, we're detached! Definitely not the lighting circuit(s) as I checked that.

Meeja

8,290 posts

272 months

Friday 2nd September 2011
quotequote all
I am still intrigued as to where the feed comes from.... Turn off the main incoming breaker on the Consumer Unit and see if it is still live.... If it is, then this will be a fun ride!

Puggit

Original Poster:

49,468 posts

272 months

Friday 2nd September 2011
quotequote all
Meeja said:
I am still intrigued as to where the feed comes from.... Turn off the main incoming breaker on the Consumer Unit and see if it is still live.... If it is, then this will be a fun ride!
I'm waiting for everyone to leave the house today before I do that! You never know what Mrs Puggit is doing on the 'net wink