Using 13 amp appliances on lighting cable circuit
Discussion
One leasehold flat that I rent out, I occasionally need electric to mow the lawn and trim a hedge etc. I neither like just letting myself in to the tenant’s flat, or to ask the tenants if I can use their electric, although they would allow me to do the same.
Outside of the flat I both have access to a lighting power connection, and to an inverter through the use of the car’s battery/engine power (landrover). With the former, the lighting power travels via a 3 amp fused spur unit, I was considering if there was a safe option of changing the 3 amp fuse for either a 5 or 13 amp fuse, whether either of those fuses with trip, thereby avoiding overheating of the lighting cable.
Outside of the flat I both have access to a lighting power connection, and to an inverter through the use of the car’s battery/engine power (landrover). With the former, the lighting power travels via a 3 amp fused spur unit, I was considering if there was a safe option of changing the 3 amp fuse for either a 5 or 13 amp fuse, whether either of those fuses with trip, thereby avoiding overheating of the lighting cable.
Whilst the fused spur could be uprated the circuit breaker is likely to be 6 amp or 10 amp at most at the consumer unit.
I assume its wired in 1.5 mm cable.
Fitting a 13amp fuse to the spur would not be advisable as you would more than likely trip the main fuse before the 13a that would be in the spur, especially if lighting was already being used by the tenant.
Inverter, generator or outdoor socket would get my vote if there isn't somewhere convenient inside that you could put one/use.
Legally where you would stand if a tenant objected to you using their power though, I'm not sure.
Petrol mower, battery strimmer not a better option?
I assume its wired in 1.5 mm cable.
Fitting a 13amp fuse to the spur would not be advisable as you would more than likely trip the main fuse before the 13a that would be in the spur, especially if lighting was already being used by the tenant.
Inverter, generator or outdoor socket would get my vote if there isn't somewhere convenient inside that you could put one/use.
Legally where you would stand if a tenant objected to you using their power though, I'm not sure.
Petrol mower, battery strimmer not a better option?
Gaspode said:
The fuse is there to protest the wiring, not the appliance. If you pull 13A through lighting cable rated at 5A you run a serious risk of overheating the wiring. Plus of course as has already been pointed out, running outside appliances with no RCD is asking for trouble.
Wiring should be protected from the breaker at the consumer unit, by putting a higher rated fuse in the spur the cable will still be protected but discrimination will not be achievedFFS.
IF the outside lighting sockets are supplied from a fused spur, then its POSSIBLE that the spur is connected via the ring final circuit.
Fused spurs should protect a 1.5mm cable minimum, which means the lawnmower will be fine provided the fuse is changed in the spur to a 13A.
If you can get into the property, try and find where the spur is fed from, RFC or lighting circuit.
IF the outside lighting sockets are supplied from a fused spur, then its POSSIBLE that the spur is connected via the ring final circuit.
Fused spurs should protect a 1.5mm cable minimum, which means the lawnmower will be fine provided the fuse is changed in the spur to a 13A.
If you can get into the property, try and find where the spur is fed from, RFC or lighting circuit.
Thanks for all the replies.
Yes i could purchase a petrol mower, but would a new electric mower recently purchased, i did not want to go down that route.
Lighting cable connection presently is a lampholder, but feeds from a spur unit, so was going to connect via the cable presently supplying the spur, with either a socket spur unit, or a second spur and a socket, thereby still procting the 3 amp lighting circuit.
Good point about checking the cable feed supplying present 3 amp spur, which will make the above safer to carry out.
Yes i could purchase a petrol mower, but would a new electric mower recently purchased, i did not want to go down that route.
Lighting cable connection presently is a lampholder, but feeds from a spur unit, so was going to connect via the cable presently supplying the spur, with either a socket spur unit, or a second spur and a socket, thereby still procting the 3 amp lighting circuit.
Good point about checking the cable feed supplying present 3 amp spur, which will make the above safer to carry out.
I have an outdoor socket wired into the supply to the porch light, specifically for cutting the front grass. Been using it happily for years.
On the one occasion I borrowed someone else's mower the circuit breaker in the house simply tripped, no drama. Hence their mower took more current than mine. But the wattage of your mower is still unknown and you haven't tried it, so we are no further forwards.
On the one occasion I borrowed someone else's mower the circuit breaker in the house simply tripped, no drama. Hence their mower took more current than mine. But the wattage of your mower is still unknown and you haven't tried it, so we are no further forwards.