I've just had some repairs / changes done to my ch system.
Persistent intermittent leak (4 years!) fixed. (poor solder joint which would weep/seal up so took until it opened up properly to find.
Zone valve failed. It would shut, but the micro switch was staying closed, which meant the boiler kept running, and the pump had to force the water via the relief valve until the boiler over heated. Replaced both zone valves with draytons (thanks to Ferg for the advice)
Moved a couple of rads from under the windows to internal walls.
Brilliant - all works really well.
Until this morning. Nothing.
On investigation, the pump wasn't running. Eventually, by using the manual switching, I managed to surprise it into life.
The pump is 4 years old. Is that normal life span for a pump, or has running it against the bypass valve shortened its life? Is it telling me that it wants to retire/expire?
I have a Grundfoss in the garage which was in use for a couple of months only, but about 4 years ago. If it's been run, but then left for 4 years, will it be any good?
Persistent intermittent leak (4 years!) fixed. (poor solder joint which would weep/seal up so took until it opened up properly to find.
Zone valve failed. It would shut, but the micro switch was staying closed, which meant the boiler kept running, and the pump had to force the water via the relief valve until the boiler over heated. Replaced both zone valves with draytons (thanks to Ferg for the advice)
Moved a couple of rads from under the windows to internal walls.
Brilliant - all works really well.
Until this morning. Nothing.
On investigation, the pump wasn't running. Eventually, by using the manual switching, I managed to surprise it into life.
The pump is 4 years old. Is that normal life span for a pump, or has running it against the bypass valve shortened its life? Is it telling me that it wants to retire/expire?
I have a Grundfoss in the garage which was in use for a couple of months only, but about 4 years ago. If it's been run, but then left for 4 years, will it be any good?
Paul Drawmer said:
..thanks to Ferg for the advice...
You are, of course, welcome Paul. You've got my number so why not!!?Pump may well be on it's last, that's not a great life expectancy! Could just be the capacitor, but sounds more like a duff winding on one of the speeds. Take the head off the Grundfos and make sure the impeller vanes are free from clag. Give it a go. It may well last years more!
You should be able to unscrew the bit in the middle of the pump body - and then check the motor spins freely.
You could also try fitting a plug and making sure it works before fitting.
I had a circulating pump fail a couple of days ago, mind you it was a cheap Chinese one 3 years old. Windings burnt out with water causing the heat pump to come up with an electrical fault.
You could also try fitting a plug and making sure it works before fitting.
I had a circulating pump fail a couple of days ago, mind you it was a cheap Chinese one 3 years old. Windings burnt out with water causing the heat pump to come up with an electrical fault.