Central Heating problems
Author
Discussion

AndyNetwork

Original Poster:

1,849 posts

225 months

Thursday 8th December 2011
quotequote all
Ok - here's the background (Sorry, it's a bit long winded!!!)

Moved into my house just short of 3 years ago, and never had a problem with my central heating (using a combi boiler) until this week when the cold weather set in.

Got the thermostat set at about 17 degrees in the hall way, and non of the radiators were red hot, some were warm, some cold.

Considering I had taken a radiator off to decorate earlier in the year, I suspected that there was air in the system.

Blead the radiators last night, and one or two had a little air in them, but not a huge amount. As a result, I needed to top the pressure up in the boiler, to bring it back to where it was.

Everything appeared to be fine, the radiators were all warming up correctly, except the one in the hall. The only one without a thermostatic valve on it.

Anyway, I did a bit of googling, and it suggested that I turn all the radiators off, and see if the cold radiator gets warm.

I did this, and it did get warm, very warm, inside an hour, the system was switching off, as the thermostat on the wall in the hall was up to 17 degrees or so.

So, I then go and turn the other radiators back on. The radiator in the hall then goes cold again.

Any ideas what could be causing this, and how I can resolve it?

Arthur Jackson

2,111 posts

261 months

Thursday 8th December 2011
quotequote all
It sounds like the system needs balancing. Have you touched any of the lockshield valves on the radiators? If not, I'd suggest the pump is failing, perhaps.

cjs

11,729 posts

282 months

Thursday 8th December 2011
quotequote all
Are you getting good hot water? IE can you run a bath or take a shower without the water going hot then cold?

When in central heating mode does the boiler fire up and stay fired up or does it keep switching off/on/off/on etc.

What make model is the boiler?


karona

1,928 posts

217 months

Thursday 8th December 2011
quotequote all
The radiators are plumbed in parallel, the water takes the path of least resistance around the system, i.e. the other rads. Once they're all off, because the thermostats are warm enough, the water can only pass through the rad in the hall. It then gets warm, and the room stat turns the boiler off because the whole house will be warm. Open the locksheild valve on the cold rad, it will warm up sooner, the room stat will shut down the boiler sooner, and the rest of the house will feel cooler. Possible the previous owner felt the cold more, and wanted the house red hot.

AndyNetwork

Original Poster:

1,849 posts

225 months

Thursday 8th December 2011
quotequote all
Thanks for the help guys, some things to consider. Out of politeness, here are the answers to your questions.

Arthur Jackson said:
It sounds like the system needs balancing. Have you touched any of the lockshield valves on the radiators? If not, I'd suggest the pump is failing, perhaps.
Only on the radiator I removed earlier this year to decorate.

cjs said:
Are you getting good hot water? IE can you run a bath or take a shower without the water going hot then cold?

When in central heating mode does the boiler fire up and stay fired up or does it keep switching off/on/off/on etc.

What make model is the boiler?
Hot water is fine, Shower is electric, so not really applicable, but can run a bath full of hot water without problems.

The boiler fires up and stays on when in C/H mode. However, I'm sure in the past it has fired, then gone off, fired and then gone off,etc. The boiler is a Worcester Bosch. Not sure of the model, but think it's 28Si.

karona said:
The radiators are plumbed in parallel, the water takes the path of least resistance around the system, i.e. the other rads. Once they're all off, because the thermostats are warm enough, the water can only pass through the rad in the hall. It then gets warm, and the room stat turns the boiler off because the whole house will be warm. Open the locksheild valve on the cold rad, it will warm up sooner, the room stat will shut down the boiler sooner, and the rest of the house will feel cooler. Possible the previous owner felt the cold more, and wanted the house red hot.
The Lockshield valve on the cold rad is fully open. The only radiator I have changed any settings on the lockvalve is the one in the dining room, when I needed to paper behind it, so took it off the wall. I suspect this is the culprit, and will turn down the lockvalve on this, and see what happens.

Cheers again!