Adding a socket on a spur
Author
Discussion

Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
I'm needing to put in an outdoor socket to run a trickle charger.

My garage has it's own feed from the main fuse board in the house.
I have a cable from the board to a socket in the garage, which in turn has a cable coming out of it to a single socket that runs the garage door opener, then this socket has a single cable down to another double. (which I assume is classed as a spur?)

If I break into this final single cable and put a fused switch in, can I then take a spur off the last socket (the existing spur) to feed the external socket?

Thanks.

Wings

5,985 posts

246 months

Friday 16th December 2011
quotequote all
Yes, with the fused socket being used with a 13 amp fuse.

Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Excellent, thanks.

Ganglandboss

8,576 posts

234 months

Friday 16th December 2011
quotequote all
It sounds like a radial circuit to me so none of the sockets would be classed as a spur. I assume it looks like this:

Consumer unit -->-- single socket -->-- single socket -->-- twin socket


What size is the cable from the consumer unit and what is the rating of the breaker? Is the circuit RCD protected? is there just one cable from the consumer unit to the socket circuit?

Also note addition of an outdoor socket outlet is notifiable under part P of the building regs.


Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Sounds about right, only there's no cable from the final socket going back to (anywhere?) to complete a ring.

I thought Part P would come into it however, the amount of people I know who do things like this, and add extra external lights etc.... and never had a problem.

Ganglandboss

8,576 posts

234 months

Friday 16th December 2011
quotequote all
At the end of the day it's your call regarding part P. The worst case scenario is there is an accident or a fire and your insurance company start trying to wriggle out of paying. Prosecution is a possibility, although I don't think there has been any for DIYers yet.

Are you confident enough with your ability to do a proper job?

Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Ganglandboss said:
At the end of the day it's your call regarding part P. The worst case scenario is there is an accident or a fire and your insurance company start trying to wriggle out of paying. Prosecution is a possibility, although I don't think there has been any for DIYers yet.

Are you confident enough with your ability to do a proper job?
Absolutely confident.

Just thought I'd double check with you guys wink

25 years of working on sites with every other trade can teach one a fair bit.

That, and the fact my house was completely renovated (inc complete re-wire etc) 6 years ago, so who's to know ....

Ganglandboss

8,576 posts

234 months

Friday 16th December 2011
quotequote all
Zyp said:
That, and the fact my house was completely renovated (inc complete re-wire etc) 6 years ago, so who's to know ....
Anyone who can see the cable is date-stamped 2011! wink


Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Not when I've got a full reel in the garage from 6 years ago laugh

Deva Link

26,934 posts

276 months

Friday 16th December 2011
quotequote all
Zyp said:
If I break into this final single cable and put a fused switch in, can I then take a spur off the last socket (the existing spur) to feed the external socket?
Don'r understand the above. It reads like you want to put a fused switch in the feed to the last socket, then spur off the socket? If that's the case then the fused switch would isolate the the last socket and whatever was spurred off it.

Is the garage circuit protected by an RCD at the main circuit board?

Ganglandboss

8,576 posts

234 months

Friday 16th December 2011
quotequote all
Deva Link said:
Don'r understand the above. It reads like you want to put a fused switch in the feed to the last socket, then spur off the socket? If that's the case then the fused switch would isolate the the last socket and whatever was spurred off it.

Is the garage circuit protected by an RCD at the main circuit board?
If you connect the phase and neutrals of the cable you're breaking into in the supply side and the cable to the new s/o into the load side it would not isolate the last socket.

Deva Link

26,934 posts

276 months

Friday 16th December 2011
quotequote all
Ganglandboss said:
If you connect the phase and neutrals of the cable you're breaking into in the supply side and the cable to the new s/o into the load side it would not isolate the last socket.
That's not what he said though. He said he'd spur off the last socket.

Ganglandboss

8,576 posts

234 months

Friday 16th December 2011
quotequote all
Oops...correct.

Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Like this -

The second last socket in the diagram is existing.


Ganglandboss

8,576 posts

234 months

Friday 16th December 2011
quotequote all
Zyp said:
Like this -

The second last socket in the diagram is existing.

That is a ring - your circuit sounds like a radial.

Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Yes, you're right - just had another look.

Basically, it's just one cable that connects all 3 sockets.

So how do I go about adding just one more single socket?
Can I just carry on with the single cable?

edit - also just re-read your first reply redface

Deva Link

26,934 posts

276 months

Friday 16th December 2011
quotequote all
Do you want to be able to turn off / isolate the outside socket (ie to stop someone random plugging something in)?

Is the garage circuit protected at the main consumer unit by an RCD?

Your best bet might be to get an outside extension socket kit then you cn just plug it in. Something like this: http://www.amazon.co.uk/Outdoor-Extension-pressure...

dickymint

29,278 posts

289 months

Friday 16th December 2011
quotequote all
Deva Link said:
Do you want to be able to turn off / isolate the outside socket (ie to stop someone random plugging something in)?

Is the garage circuit protected at the main consumer unit by an RCD?

Your best bet might be to get an outside extension socket kit then you cn just plug it in. Something like this: http://www.amazon.co.uk/Outdoor-Extension-pressure...
thumbup as it negates any Part P requirement.

Zyp

Original Poster:

16,189 posts

220 months

Friday 16th December 2011
quotequote all
Deva Link said:
Do you want to be able to turn off / isolate the outside socket (ie to stop someone random plugging something in)?

Is the garage circuit protected at the main consumer unit by an RCD?

Your best bet might be to get an outside extension socket kit then you cn just plug it in. Something like this: http://www.amazon.co.uk/Outdoor-Extension-pressure...
I was only going to put a fused switch in line as an extra safety precaution - water ingress etc within the outdoor socket.
The garage circuit is protected at the main CU with an RCD, yes.

The above link looks good, but I may as well do a hard wire - would amount to the same thing?

Deva Link

26,934 posts

276 months

Friday 16th December 2011
quotequote all
Zyp said:
The above link looks good, but I may as well do a hard wire - would amount to the same thing?
Pretty well, yes. The only snag with putting the switch/fuse (at 13A) unit before a couple of sockets is that if plug in a couple things with a chunky load then you'll blow the fuse. Say you have 3KW fan heater running and then someone starts up a power washer outside, the total current taken will blow the 13A fuse.