Quick electrical question

Author
Discussion

119

Original Poster:

12,305 posts

51 months

Tuesday 8th April
quotequote all
Friend of mine has a shop with ceiling panels and square 4 way flourescent fittings and we swapped them out for JC led panels.

There are about 15 in place now and every time he switches them on the circuit trips in the fuse box.

If he resets it they seems to then stay on.

This keeps happening and I read that led can have a high start power which can cause this to happen?

Is there an easy way to solve this?

Someone mentioned getting someone in to change the fuse breaker to a C model or a 10amp b model

caziques

2,736 posts

183 months

Tuesday 8th April
quotequote all

D curve breaker is possibly what is required.

Used where there can be a high inrush current.

megaphone

11,226 posts

266 months

Wednesday 9th April
quotequote all
Is the circuit breaker tripping (MCB) or the RCD? What rating is the MCB?

119

Original Poster:

12,305 posts

51 months

Wednesday 9th April
quotequote all
It is the circuit breaker and it’s a b6(?)

He dug out the invoice and its these...


https://jcc.co.uk/products/jc080218

Edited by 119 on Wednesday 9th April 08:11

megaphone

11,226 posts

266 months

Wednesday 9th April
quotequote all
The link says the panels are 30w each x15 = 450w. So around 2 amps. Well within the rating of the 6 amp breaker.

Has he checked the cabling and connections? Is there anything else connected on the circuit?

Richard-D

1,491 posts

79 months

Wednesday 9th April
quotequote all
megaphone said:
The link says the panels are 30w each x15 = 450w. So around 2 amps. Well within the rating of the 6 amp breaker.
You're right that the rating is fine for the average current draw. As pointed out above though, the inrush current will be far higher.

Mr Pointy

12,557 posts

174 months

Wednesday 9th April
quotequote all
If the panels are dimmable then change the switch to a dimmer switch which will soft start on switch on.

119

Original Poster:

12,305 posts

51 months

Wednesday 9th April
quotequote all
Thanks all.

No there is no dimmer on any of them as it’s for a shop and there is no need to dim them.

The set up is, a main switch by the door that turns off all the lights and a selection of sockets and this controls a big contact switch?

There are around 25 lights in total, and it’s actually 18 on one mcb circuit and 8 on another mcb circuit.

The one with 8 is fine but the other one is the one that trips.

megaphone

11,226 posts

266 months

Wednesday 9th April
quotequote all
So the circuit is on a contactor? That could be causing an issue when it activates.

Simpo Two

89,134 posts

280 months

Wednesday 9th April
quotequote all
119 said:
There are around 25 lights in total, and it’s actually 18 on one mcb circuit and 8 on another mcb circuit.

The one with 8 is fine but the other one is the one that trips.
Can you change the wiring so it's 13 + 13 rather than 18 + 8?

119

Original Poster:

12,305 posts

51 months

Wednesday 9th April
quotequote all
megaphone said:
So the circuit is on a contactor? That could be causing an issue when it activates.
Contactor that’s it.

So, just found that the whole separate fuse box with these lights and other sockets is controlled by the contactor.

ie the mains cables to feed the fuse box are fed from this contactor.

If that makes sense biggrin

As for rewiring, possibly but the mess of cables above the ceiling is quite staggering and it may be tricky to see which cables are which!

He has ordered 2 x C6 mcbs to try but he can do that.


119

Original Poster:

12,305 posts

51 months

Wednesday 9th April
quotequote all
Forgot to mention that we disconnected two and it seems to behave.

119

Original Poster:

12,305 posts

51 months

Monday 14th April
quotequote all
Just to close this off, he changed the fuse breakers to the C type and all is good.