2 Pole Isolator Question
Author
Discussion

Too Late

Original Poster:

5,139 posts

257 months

Saturday 28th June 2025
quotequote all
I need to wire in an isolator switch this weekend. It's for an air source heat pump.

Can I just double check this. L1 will be incoming live, L3 will be incoming live.
T1 is live to appliance. T3 is neutral to appliance

It's a BG 2P AX 32a ip65 isolator switch.





Incoming Supply:
Live -> 1/L1
Neutral -> 5/L3

Outgoing Load:
Live -> 2/T1
Neutral -> 6/T3

Earth to Earth terminal (side metal block)


Edited by Too Late on Saturday 28th June 16:24

Yabu

2,090 posts

223 months

Saturday 28th June 2025
quotequote all
Too Late said:
I need to wire in an isolator switch this weekend. It's for an air source heat pump.

T1 is live to appliance. T3 is neutral to appliance
Incoming Supply:
Live -> 1/L1
Neutral -> 5/L3

Outgoing Load:
Live -> 2/T1
Neutral -> 6/T3

Earth to Earth terminal (side metal block)
Yes
Both cables want to come into the bottom of the isolator if it’s fitted outside (unless cables coming through a wall)
Don’t drill the top as water will get in.


Edited by Yabu on Saturday 28th June 17:01

Too Late

Original Poster:

5,139 posts

257 months

Saturday 28th June 2025
quotequote all
Fantastic. Thanks for replying.

caziques

2,800 posts

190 months

Saturday 28th June 2025
quotequote all

Is it normal in the UK to switch the live and the neutral?

finlo

4,132 posts

225 months

Saturday 28th June 2025
quotequote all
Yes, because the neutral can be live in some circumstances.

LastPoster

3,118 posts

205 months

Saturday 28th June 2025
quotequote all
To an Air Source Heat Pump, yes.

caziques

2,800 posts

190 months

Sunday 29th June 2025
quotequote all

Interesting.

Here in NZ, electrical boards are MEN (multiple earth neutral). All earths are joined on a big long brass bar, all the neutrals are joined on another - then the two bars are joined together. Not forgetting a big earth wire attached to a stake in the ground. Only the live wire is switched.