Fixing Expansion tank back on wall
Fixing Expansion tank back on wall
Author
Discussion

craig1912

Original Poster:

4,632 posts

141 months

Friday 10th July
quotequote all
Some clown thought a couple of rawl plugs through plaster board was enough to fix expansion tank to the wall. Woken last night as it fell off!

What are the best fixing to secure it properly. It s an external wall and there is a small gap behind the plasterboard and then the thermal grey blocks.

Would bigger rawl plugs into the thermal block be OK?




craigthecoupe

1,064 posts

233 months

Friday 10th July
quotequote all
Is the plasterboard on studwork, or dot and dab? Probably better trying to get something solid. Whats the gap like behind the board? If its too large I imagine the fixings will sag in time?

wolfracesonic

9,204 posts

156 months

Friday 10th July
quotequote all
Rigifix or similar.

JoshSm

5,035 posts

66 months

Friday 10th July
quotequote all
Depending on the weight maybe fix it to a board and then fix the board to the wall, four fixings over a wider area is always going to be better than two close together.


Mr Pointy

13,361 posts

188 months

Friday 10th July
quotequote all
Corefix - the red boxes, not the blue & green. They bridge the gap into the blockwork.

https://www.amazon.co.uk/s?k=corefix&crid=1A82...
https://www.screwfix.com/c/screws-nails-fixings/wa...

craig1912

Original Poster:

4,632 posts

141 months

Friday 10th July
quotequote all
Mr Pointy said:
Corefix - the red boxes, not the blue & green. They bridge the gap into the blockwork.

https://www.amazon.co.uk/s?k=corefix&crid=1A82...
https://www.screwfix.com/c/screws-nails-fixings/wa...
Thanks- was just looking at these after watching a you tube video

https://www.screwfix.com/p/corefix-connect-heavy-d...


craig1912

Original Poster:

4,632 posts

141 months

Friday 10th July
quotequote all
craigthecoupe said:
Is the plasterboard on studwork, or dot and dab? Probably better trying to get something solid. Whats the gap like behind the board? If its too large I imagine the fixings will sag in time?
It’s dot and dab- gap is only 5-10 mm so Corefix look ideal

wolfracesonic

9,204 posts

156 months

Friday 10th July
quotequote all
Corefix, very similar to Rigifix I believescratchchin

craig1912

Original Poster:

4,632 posts

141 months

Friday 10th July
quotequote all
wolfracesonic said:
Corefix, very similar to Rigifix I believescratchchin
👍

Magic919

14,493 posts

230 months

Friday 10th July
quotequote all
Would be worth checking it hasn’t failed.

craig1912

Original Poster:

4,632 posts

141 months

Friday 10th July
quotequote all
Magic919 said:
Would be worth checking it hasn t failed.
Didn’t fall far but how would I check it hasn’t failed?

Magic919

14,493 posts

230 months

Friday 10th July
quotequote all
They don’t fail because of falling. They double in weight when they fail and fall off the wall.

Does it still have air and pressure or is it full of water?

craig1912

Original Poster:

4,632 posts

141 months

Friday 10th July
quotequote all
Magic919 said:
They don t fail because of falling. They double in weight when they fail and fall off the wall.

Does it still have air and pressure or is it full of water?
Feels quite heavy and there is water in there but not full of water. Pressure dial is normal. I don’t know much about this stuff so probably get a plumber out to check.
Hot water seems normal.

Mike Legerwood

100 posts

4 months

Sunday 12th July
quotequote all
I prefer DryLine Pro to the corefix version.

https://www.drylinepro.com/

Mr Pointy

13,361 posts

188 months

Sunday 12th July
quotequote all
Mike Legerwood said:
I prefer DryLine Pro to the corefix version.

https://www.drylinepro.com/
Why, what makes them better?

craig1912

Original Poster:

4,632 posts

141 months

Sunday 12th July
quotequote all
I’ve ordered the Corefix ones now

ducatikim

26 posts

9 months

Sunday 12th July
quotequote all
craig1912 said:
Feels quite heavy and there is water in there but not full of water. Pressure dial is normal. I don t know much about this stuff so probably get a plumber out to check.
Hot water seems normal.
Assuming that the heating system is cold and the hot water tank isn't calling, there should be no, or next to no water in the expansion vessel.
The precharge should be set to the same pressure as the cold fill pressure in the system. Isolate, drain down and re-charge the vessel via the schrader valve on top.
As previously mentioned, not unknown for the rubber membrane or bag to fail, in which case replace as required.

Eta Why don't so called heating engineers ever carry out the simple check on precharge when they're doing a boiler service?

Edited by ducatikim on Sunday 12th July 14:31

craig1912

Original Poster:

4,632 posts

141 months

Monday 13th July
quotequote all
Probably going to get someone in to check over once I ve remounted on the wall.
How do I get access to the Schrader valve?




Magic919

14,493 posts

230 months

Monday 13th July
quotequote all
Try the other end.

spitfire-ian

4,219 posts

257 months

Monday 13th July
quotequote all
ducatikim said:
Eta Why don't so called heating engineers ever carry out the simple check on precharge when they're doing a boiler service?
Ours plumber checks ours when doing a boiler service. He's quite pricey compared to others though but does do a very thorough job with anything we've asked him to do. He does also have a tendency to go off abroad skiing/surfing/lounging around when he feels like it hehe