Electrical wiring (strip lighting) question
Discussion
I'm putting some additional lighting in the garage and note in the instructions with the strip lights (fluorescent tubes) that it says 'this appliance must be earthed'.
In the little connection box within the tube assembly, there's a live and neutral (going to various gubbins within the tube assembly) but the earth connector is connected to nothing - there's no wire that would go from my earth to anywhere. Is this normal?
Thanks
N
Is it a plastic enclosure or is it a metal one and you have not noticed the little metal tab going into the connector? If it is the former it will not need an earth connection to the case but it must still have somewhere to terminate your earth should you extend the circuit, install a switch wire from it or replace it with a metal bodied fitting in the future.
Dave - qualified spark.
Dave - qualified spark.
NDA said:
PS Dave, just out of interest, if I hadn't earthed the fitting, what happens? Is there a risk of shock or fire? Just curious, I'm not going to do it of course!
The earth (or Circuit Protective Conductor (CPC)) is there to carry fault current should the case become live. A very high current will flow as a result and the protective device (fuse or MCB) will operate and disconnect the supply. If you don't connect it, it may well operate without a problem indefinitely but it sure ain't worth chancing it!Gassing Station | The Pie & Piston Archive | Top of Page | What's New | My Stuff