Plumbing Q - buzzing 3 way valve
Discussion
Got a fairly standard hot water/heating system with a boiler & hot and cold tanks. Next to the hot tank in the airing cupboard is a three way motorised valve - again fairly standard thing as far as I know.
While it seems to work OK (i.e. I can have the system running hot water only, heating only or both) I've noticed of late that sometimes after the time clock has switched the system off this thing is occasionally left buzzing like a demented wasp. A quick trip downstairs to the master switch next to the timeclock & switch it off & back on again & it stops.
So is it on its way out & if so can you just replace the electric part of it or is it a system drain down & have to replace the whole unit kind of job?
While it seems to work OK (i.e. I can have the system running hot water only, heating only or both) I've noticed of late that sometimes after the time clock has switched the system off this thing is occasionally left buzzing like a demented wasp. A quick trip downstairs to the master switch next to the timeclock & switch it off & back on again & it stops.
So is it on its way out & if so can you just replace the electric part of it or is it a system drain down & have to replace the whole unit kind of job?
This happened to me on a similar valve.
Basically the mechanical part (vane thing in the 3-way valve) was in the process of seizing and the electrical part was struggling to turn the valve. So it eventually died...
Drain and replace is probably the best. About £50 for the part (try screwfix)
HTH