quotequote all
I'm in the middle of fitting a new kitchen and with it, wanting to get the boiler replaced.

Now everything is out of the kitchen it appears the gas pipe coming from the meter is a steel pipe with an external diameter of about 1 inch. I assume this is 3/4 BSP.

Now I have had a few gas fitters around to quote and they are umming and arring about needing to fit a new 22mm pipe straight from the gas meter (which would be a right messy pain in the arse).

The existing boiler is 28 kW and I've not had an issue with it. The new boiler would be a 28 kW Worchester Bosch.

I thought the bore of 3/4 BSP steel pipe and 22mm copper was very similar so my thoughts were they should just be able to couple the 3/4 BSP to 22mm copper which would go up to the boiler or am I being simple?

Edited by Neil_Sc on Thursday 9th April 12:06

Ferg

15,242 posts

259 months

Thursday 9th April 2009
quotequote all
They should stop guessing and do the calculations.

Glassman

22,650 posts

217 months

Thursday 9th April 2009
quotequote all
Ferg said:
They should stop guessing and do the calculations.
Do you reckon?


Ferg

15,242 posts

259 months

Thursday 9th April 2009
quotequote all
Well it might help.

All this 'is it?', 'isn't it?' st!!! rolleyes

Glassman

22,650 posts

217 months

Thursday 9th April 2009
quotequote all
Ferg said:
Well it might help.

All this 'is it?', 'isn't it?' st!!! rolleyes
---> scratchchin

wink

Ferg

15,242 posts

259 months

Thursday 9th April 2009
quotequote all
laugh

Neil_Sc

Original Poster:

2,251 posts

209 months

Thursday 9th April 2009
quotequote all
Now the electrician has been today and cut a load of holes in the ceiling, I can more of less see the route of the pipe and count total length at 5.5 Meters with 7 elbows along the way. Do elbows count as 0.6 M? If so, the total pipe run is 9.7 Meters.

I will have no other appliances making use of gas.

bmt216a

294 posts

243 months

Thursday 9th April 2009
quotequote all
An elbow = 0.5m

As long as you have a min 3/4" running from meter, I would be happy to intall a condensing boiler. Worst case, once boiler is installed with original gas pipe and the gas rate is correct, you shouldn't have a problem.