Any warehouse heater (blower) experts in here?
Discussion
I'd be more inclined to get radiant tube heaters as opposed to tin puffers...
http://www.ambirad.co.uk/htm/ambirad/php/index.php
http://www.rg-inc.com/uk/BHL-infrared-gas-heater.h...
All depends on the layout and what the space is used for...
http://www.ambirad.co.uk/htm/ambirad/php/index.php
http://www.rg-inc.com/uk/BHL-infrared-gas-heater.h...
All depends on the layout and what the space is used for...
What about the building is it insulated, is there any/much glass in it.
What is stored in it, is the building in constant use, e.g forklifts in and out all the time, or is it just storage with a delivery/collection once a week?
Sorry to get your hopes up, but INE just asking some (hopefully) relevant questions to let an expert get a better idea of what's needed.
What is stored in it, is the building in constant use, e.g forklifts in and out all the time, or is it just storage with a delivery/collection once a week?
Sorry to get your hopes up, but INE just asking some (hopefully) relevant questions to let an expert get a better idea of what's needed.
Edited by John MacK on Friday 12th February 09:16
We used to use one of these type of blowers
http://www.andrews-sykes.com/heaters/oil-fired-hea...
to heat a 2000 sqft warehouse, running costs were about £100 a week. You can get that down by having a bunded tank for fuel if you're in it for the long term, we used to buy barrels which is more expensive. Fit an external flue and a top tip is make sure that the thermostat is somewhere your staff can't get at it otherwise they'll turn it into a tropical butterfly house.
http://www.andrews-sykes.com/heaters/oil-fired-hea...
to heat a 2000 sqft warehouse, running costs were about £100 a week. You can get that down by having a bunded tank for fuel if you're in it for the long term, we used to buy barrels which is more expensive. Fit an external flue and a top tip is make sure that the thermostat is somewhere your staff can't get at it otherwise they'll turn it into a tropical butterfly house.
Radiant tubes are meant to be more efficient, as they heat objects rather than the air...
http://www.pwemag.co.uk/index.php?page=273&sho...
With air blowers, as soon as you open the roller shutter, most of the warm air goes straight out... also, you'll need/benefit from destrat. fans to push the warm air down...
It sounds like you only need frost protection anyway, so I'd be surprised if you needed the tube heaters on for more than an hour a day...
http://www.pwemag.co.uk/index.php?page=273&sho...
With air blowers, as soon as you open the roller shutter, most of the warm air goes straight out... also, you'll need/benefit from destrat. fans to push the warm air down...
It sounds like you only need frost protection anyway, so I'd be surprised if you needed the tube heaters on for more than an hour a day...
Edited by Dave^ on Friday 12th February 10:16
How much heat is going to be lost, and is there anything at all you can do to prevent or reduce this? Every pound spent reducing the heat loss will be more than recouped against the lowered heating bills.
I work in a large (for one man) unit with virtually nothing in the way of insulation and tried everything. In the end I gave up trying to heat it, and instead partioned off a smaller area with its own ceiling. I don't suppose that is going to work for you, but maybe?
I work in a large (for one man) unit with virtually nothing in the way of insulation and tried everything. In the end I gave up trying to heat it, and instead partioned off a smaller area with its own ceiling. I don't suppose that is going to work for you, but maybe?
Have you considered one of these, possibly with ductwork?
http://www.powrmatic.co.uk/cabinet_heaters
They are good units, I have designed a few ducted systems for these, although clients were providing the units so not sure on costs but I think they were £2 - 3k rougly. Advantage with duct is you can direct the warm air to where you need it. A large unit may even do both your areas if you duct it.
http://www.powrmatic.co.uk/cabinet_heaters
They are good units, I have designed a few ducted systems for these, although clients were providing the units so not sure on costs but I think they were £2 - 3k rougly. Advantage with duct is you can direct the warm air to where you need it. A large unit may even do both your areas if you duct it.
You can buy/lease fan units which redirect hot air from the roof down to floor level, these have 2 advantages:
1) As the hot air rises, gets it back down to where people are.
2) Because the air against the roof is cooler, heat loss through the roof is reduced.
Typically savings equate to 3 times purchase/lease costs for the units, and they are being used by a lot of supermarkets who recognise their value.
PM me if you need more info.
1) As the hot air rises, gets it back down to where people are.
2) Because the air against the roof is cooler, heat loss through the roof is reduced.
Typically savings equate to 3 times purchase/lease costs for the units, and they are being used by a lot of supermarkets who recognise their value.
PM me if you need more info.
Wouldnt it be cheaper to buy all the staff a uniform that includes a couple of jumpers and allow them to wear shorts in the summer?!
When I used to work in warehouses the heating / cooling was always a source of arguments.
In the winter:
The middle aged 'mentals' that tended not to be placed in a physical job always wanted the place at least as hot as the earths core.
Everyone doing the grunt work would want the heat off completely.
In the summer:
The middle aged 'mentals' that tended not to be placed in a physical job always wanted the place at least as hot as the earths core.
Everyone doing the grunt work would want the ceiling fans, portable fans and air con going (if the place had it) but often the management sorts would not allow us to have any of this stuff switched on?!
In fact I remember one summer that was particularly hot they removed the portable fans completely!!
When I used to work in warehouses the heating / cooling was always a source of arguments.
In the winter:
The middle aged 'mentals' that tended not to be placed in a physical job always wanted the place at least as hot as the earths core.
Everyone doing the grunt work would want the heat off completely.
In the summer:
The middle aged 'mentals' that tended not to be placed in a physical job always wanted the place at least as hot as the earths core.
Everyone doing the grunt work would want the ceiling fans, portable fans and air con going (if the place had it) but often the management sorts would not allow us to have any of this stuff switched on?!
In fact I remember one summer that was particularly hot they removed the portable fans completely!!