Armoured Cable
Discussion
Going to be installing a 500watt Halogen some distance from the house.
Got access to a digger tomorrow so need to buy the cable and dig in, connections can come later.
Is there a spark out there who can calculate the size of armoured cable I should buy for a 75metre run, to support a 500watt halogen light on the end.
Cheers Tazzatime
Got access to a digger tomorrow so need to buy the cable and dig in, connections can come later.
Is there a spark out there who can calculate the size of armoured cable I should buy for a 75metre run, to support a 500watt halogen light on the end.
Cheers Tazzatime
Smiler. said:
Is it fed via an RCD/RCBO? If not, you will need to check the Earth-loop impedance.
Is the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
Hi SmilerIs the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
I intended to use 3-core, thanks for the advice on the RCD/RCBO, I have a pal who is a qualified electrician who I will get to do the installation. But cannot contact him at the moment and need to get the cable dug in before I will be able to talk to him.
Cheers
tazzatime said:
Smiler. said:
Is it fed via an RCD/RCBO? If not, you will need to check the Earth-loop impedance.
Is the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
Hi SmilerIs the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
I intended to use 3-core, thanks for the advice on the RCD/RCBO, I have a pal who is a qualified electrician who I will get to do the installation. But cannot contact him at the moment and need to get the cable dug in before I will be able to talk to him.
Cheers
As Plotters says, 1kw is fine on 1.5mm² SWA, but doesn't leave much over if it's an existing circuit. You can get 100W & 200W linear TH lamps, but at 75m, 500W might be needed.
Smiler. said:
tazzatime said:
Smiler. said:
Is it fed via an RCD/RCBO? If not, you will need to check the Earth-loop impedance.
Is the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
Hi SmilerIs the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
I intended to use 3-core, thanks for the advice on the RCD/RCBO, I have a pal who is a qualified electrician who I will get to do the installation. But cannot contact him at the moment and need to get the cable dug in before I will be able to talk to him.
Cheers
As Plotters says, 1kw is fine on 1.5mm² SWA, but doesn't leave much over if it's an existing circuit. You can get 100W & 200W linear TH lamps, but at 75m, 500W might be needed.
tazzatime said:
Smiler. said:
tazzatime said:
Smiler. said:
Is it fed via an RCD/RCBO? If not, you will need to check the Earth-loop impedance.
Is the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
Hi SmilerIs the cable terminating at a metallic enclosure? If not, would be worth using 3-core to provide Live/Neutral/Earth (I usually spec that anyway, just to be safe).
I intended to use 3-core, thanks for the advice on the RCD/RCBO, I have a pal who is a qualified electrician who I will get to do the installation. But cannot contact him at the moment and need to get the cable dug in before I will be able to talk to him.
Cheers
As Plotters says, 1kw is fine on 1.5mm² SWA, but doesn't leave much over if it's an existing circuit. You can get 100W & 200W linear TH lamps, but at 75m, 500W might be needed.
75m is a fair distance and you will get volt drop, you'd be aswell putting 2.5mm in just to cover yourself.
Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
Raverbaby said:
75m is a fair distance and you will get volt drop, you'd be aswell putting 2.5mm in just to cover yourself.
Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
The cable needs to be sized for the size of the breaker protecting it, not the load. A lighting circuit on a 6A breaker requires a cable size of 4mm according to that website (my copy of the wiring regs is at the office so I cannot check it properly right now).Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
Edited by Ganglandboss on Thursday 19th August 19:52
Ganglandboss said:
Raverbaby said:
75m is a fair distance and you will get volt drop, you'd be aswell putting 2.5mm in just to cover yourself.
Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
The cable needs to be sized for the size of the breaker protecting it, not the load. A lighting circuit on a 6A breaker requires a cable size of 4mm according to that website (my copy of the wiring regs is at the office so I cannot check it properly right now).Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
Edited by Ganglandboss on Thursday 19th August 19:52
From the website:-
Required Cable Size 2.5 mm
Voltage Drop 5.22 Volts.
Percentage Drop 2.3%
Current Load 4.00 Amps
Max Cable Load* 24.9 Amps
My big red books in the van and I cant be arsed going out cos its been a long day
Raverbaby said:
Ganglandboss said:
Raverbaby said:
75m is a fair distance and you will get volt drop, you'd be aswell putting 2.5mm in just to cover yourself.
Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
The cable needs to be sized for the size of the breaker protecting it, not the load. A lighting circuit on a 6A breaker requires a cable size of 4mm according to that website (my copy of the wiring regs is at the office so I cannot check it properly right now).Have a wee butchers at this guide, it suggests 2.5mm.
http://www.tlc-direct.co.uk/Technical/Charts/Volta...
Edited by Ganglandboss on Thursday 19th August 19:52
From the website:-
Required Cable Size 2.5 mm
Voltage Drop 5.22 Volts.
Percentage Drop 2.3%
Current Load 4.00 Amps
Max Cable Load* 24.9 Amps
My big red books in the van and I cant be arsed going out cos its been a long day
The cable sizing calcs have to be based on the highest potential load which the cable could carry (which is the same as the rating of the breaker) rather than the actual load.
Gassing Station | Homes, Gardens and DIY | Top of Page | What's New | My Stuff