Huge Fire In Block Of Flats
Discussion
jsf said:
Gas appliances cut gas flow if they lose their heat at the flow point, which happens when the supply is cut off.
There should be no issue with safety reinstating the main supply to a building with appliances working properly.
But each flat still needs to be checked to ensure that they are working correctly.There should be no issue with safety reinstating the main supply to a building with appliances working properly.
jsf said:
Gas appliances cut gas flow if they lose their heat at the flow point, which happens when the supply is cut off.
There should be no issue with safety reinstating the main supply to a building with appliances working properly.
But each flat still needs to be checked to ensure that they are working correctly.There should be no issue with safety reinstating the main supply to a building with appliances working properly.
jmorgan said:
AW111 said:
spaximus said:
The rules are there to protect people and there are enough communal parks and gardens even in London to allow most activities. Do you think the "rich" who own flats thinks "fk it" I will have a barbeque on my balcony? No they understand if they want a garden they pay more for one or do without.
IIRC the cladding fire in Melbourne was started by a balcony barbecue - in a "rich person's" flat.When I was in an apartment, I had my BBQ going most weekends on the balcony. Most are gas though.
Enough room for an 8 seater table, a long bench seat, and a big BBQ.
I recon every apartment is the same, from friends places and looking at the occupied apartments. If you see chairs on the balcony, you'll 99% see a BBQ too.
Bibbs said:
In Australia it's very common.
When I was in an apartment, I had my BBQ going most weekends on the balcony. Most are gas though.
Enough room for an 8 seater table, a long bench seat, and a big BBQ.
I recon every apartment is the same, from friends places and looking at the occupied apartments. If you see chairs on the balcony, you'll 99% see a BBQ too.
Yep, same. I rented a nice 2 bedroom apartment in central Newcastle that had a similar sized balcony. Used my BBQ often, and I think at lest 50-60% of other residents did as well. When I was in an apartment, I had my BBQ going most weekends on the balcony. Most are gas though.
Enough room for an 8 seater table, a long bench seat, and a big BBQ.
I recon every apartment is the same, from friends places and looking at the occupied apartments. If you see chairs on the balcony, you'll 99% see a BBQ too.
Bibbs said:
In Australia it's very common.
When I was in an apartment, I had my BBQ going most weekends on the balcony. Most are gas though.
Enough room for an 8 seater table, a long bench seat, and a big BBQ.
I recon every apartment is the same, from friends places and looking at the occupied apartments. If you see chairs on the balcony, you'll 99% see a BBQ too.
According to spaximus, you must be poor and feckless, along with your friends. When I was in an apartment, I had my BBQ going most weekends on the balcony. Most are gas though.
Enough room for an 8 seater table, a long bench seat, and a big BBQ.
I recon every apartment is the same, from friends places and looking at the occupied apartments. If you see chairs on the balcony, you'll 99% see a BBQ too.
Welshbeef said:
So given McDonnells murder claim of the govt on the tower block victims when is he going to realise it's the whole govt the whole planning and building regs and likely illegal products being used.
Nasty man saying vile things without the facts.
You agrree in principle with what he said then,, but want ALL recent governments to be included in his accusationNasty man saying vile things without the facts.
Do we yet have proof of who is to
blame and the illegality of products being used?
Nasty man saying vile things without the facts.
Fwiw, I disagree strongly with the murder claim. Could yet end up in a corporate manslaughter case though.
AW111 said:
According to spaximus, you must be poor and feckless, along with your friends.
Yup, can't disagre Granted the prices have dropped massively of late (over supply, local casino extension, golf course closure), but still over 500,000 (GBP) in the current market.
https://www.realestate.com.au/property/902-21-bow-...
Spec says 172 sq m of "land", and 112 sq m of "building". So 60 sq m of patio. I've lived in smaller houses in the UK.
Edited by Bibbs on Wednesday 28th June 07:06
Interesting short video of the Camden block that was evacuated - I'd have liked to see a much longer one though.
http://www.bbc.co.uk/news/uk-england-london-403576...
One of the comments was a fire door that would only last 5-10 minutes as 'due to health & safety' it had loads of glass panels for visual access - this seems surprising as I've seen many full panel glass fire doors that are meant to be FD60 (60 minute resistant).
Seems very odd
http://www.bbc.co.uk/news/uk-england-london-403576...
One of the comments was a fire door that would only last 5-10 minutes as 'due to health & safety' it had loads of glass panels for visual access - this seems surprising as I've seen many full panel glass fire doors that are meant to be FD60 (60 minute resistant).
Seems very odd
jsf said:
Gas appliances cut gas flow if they lose their heat at the flow point, which happens when the supply is cut off.
There should be no issue with safety reinstating the main supply to a building with appliances working properly.
Not all. My parents old cooker had no flame failure device, and they only replaced that a few weeks ago. I expect there will still be plenty about, especially in poorer households.There should be no issue with safety reinstating the main supply to a building with appliances working properly.
Ganglandboss said:
jsf said:
Gas appliances cut gas flow if they lose their heat at the flow point, which happens when the supply is cut off.
There should be no issue with safety reinstating the main supply to a building with appliances working properly.
Not all. My parents old cooker had no flame failure device, and they only replaced that a few weeks ago. I expect there will still be plenty about, especially in poorer households.There should be no issue with safety reinstating the main supply to a building with appliances working properly.
I can't begin to imagine the st storm if that happened across 120 flats every time the alarm went off!
It doesn't have to be evey time the alarm goes off. In disabled housing it can be set up so if the detectors within a flat go off only the gas to that one flat is shut off, the gas to the whole block is only shut off if a communal area detector is activated or 2 adjacent detectors within a certain timeframe of each other, and no one should be burning toast in the stairwell. Addressable panels can be pretty versatile, especially when connected to a plc or similar.
Ganglandboss said:
Not all. My parents old cooker had no flame failure device, and they only replaced that a few weeks ago. I expect there will still be plenty about, especially in poorer households.
I doubt social housing tenants would be allowed these, most tend to be quite tightly controlling of tenants gas appliances, but privatly owned is pretty much a free for all.OldGermanHeaps said:
It doesn't have to be evey time the alarm goes off. In disabled housing it can be set up so if the detectors within a flat go off only the gas to that one flat is shut off, the gas to the whole block is only shut off if a communal area detector is activated or 2 adjacent detectors within a certain timeframe of each other, and no one should be burning toast in the stairwell. Addressable panels can be pretty versatile, especially when connected to a plc or similar.
The poster I was responding to suggested cutting off the building's gas in response to a fire alarm. I'm sure there are more sensible ways to do it as you suggest, although I'm not entirely sure it's necessary in most cases. By what I've seen of Grenfell it would have to be a valve controlling supply to the whole block (the affected pipes were before the individual meter points).jsf said:
There has to be an annual inspection and certification for gas appliances in rented accommodation. Old appliances fail.
I would expect any private owners in these blocks would have to maintain that.
I own a private flat and I can do whatever I like, no one has any interest in what gas appliances I have. The hob is 15 years old and was here when I moved in, I've not had it checked and couldn't tell you if it has a cut off device. I know if I don't quite light it properly then it quite merrily chucks gas out into the room until I notice so I doubt it does have a cut off.I would expect any private owners in these blocks would have to maintain that.
If I rented it out then I'd need to get it checked.
jsf said:
There has to be an annual inspection and certification for gas appliances in rented accommodation. Old appliances fail.
I would expect any private owners in these blocks would have to maintain that.
I would expect any private owners in these blocks would have to maintain that.
OldGermanHeaps said:
Ganglandboss said:
Not all. My parents old cooker had no flame failure device, and they only replaced that a few weeks ago. I expect there will still be plenty about, especially in poorer households.
I doubt social housing tenants would be allowed these, most tend to be quite tightly controlling of tenants gas appliances, but privatly owned is pretty much a free for all.Edited by Ganglandboss on Wednesday 28th June 12:14
Blue Oval84 said:
I own a private flat and I can do whatever I like, no one has any interest in what gas appliances I have. The hob is 15 years old and was here when I moved in, I've not had it checked and couldn't tell you if it has a cut off device. I know if I don't quite light it properly then it quite merrily chucks gas out into the room until I notice so I doubt it does have a cut off.
If I rented it out then I'd need to get it checked.
This. If I rented it out then I'd need to get it checked.
I rented for years in various places with the missus before we bought our own place. Not once were we ever required to use gas appliances that met a certain safety standard or criteria. In the places they were already installed, they were never checked or had any record of being checked. There may well have been something within the contract but nothing was ever enforced or checked at the regular inspections (to make sure we hadn't trashed the place).
Regarldess what rules and regulations exist (do they?) to keep rented accommodation in check, I've seen no evidence of it ever being enforced.
Gassing Station | News, Politics & Economics | Top of Page | What's New | My Stuff