Ask an Electrician anything...

Ask an Electrician anything...

Author
Discussion

ruggedscotty

Original Poster:

5,627 posts

210 months

Friday 5th April
quotequote all
As someone who deals with electrical safety , I will tell you that those pen sticks are only to be used for tracing purposes.

They SHOULD NOT be used to prove or confirm dead any electrical circuit. especially one that your about to put your fingers on.

If undertaking any electrical work,

Identify the circuit or equipment to be worked on.

Isolate and secure the point of isolation. Also if doing it properly you would be fitting a caution sign 'Do Not Touch' on your point of isolation.

Once secured then you have to prove / confirm dead. prove or confirm is exactly the same thing, only difference is to do with safety documentation, and you wont be doing that.... But you still need to prove / confirm dead and that is by the use of an appropriate testing device to GS38 standards that gives a positive identification of live equipment.

You would test the tester before doing the prove/confirm then test the tester right after.

I have a huge dislike for tester screwdrivers or non contact testers. Mains is dangerous, and it has the capacity to kill you. too many lulled into a false sense of security.

ccr32

1,981 posts

219 months

Saturday 6th April
quotequote all
This might be a question more appropriate for the EV section of the forum, but I am unsure what I need here from an electrical perspective.

I would like an EV compatible 3 pin plug on the front of the house (such as this: https://www.screwfix.com/p/masterplug-ip66-13a-1-g... - we only have a small capacity EV so don't really need a fast charger, but I'm reluctant to use the granny lead off one of our garage sockets long term as I don't know what the wiring is like upstream of that.

I understand that even for the above linked RCBO protected EV socket, I'd also need (as found in a post on another forum):
  • A specific final circuit for the charge point or socket - no problem, can run an independent cable to it from the CU which is in the garage
  • Over current protection for the cable and the equipment- normally a 32A MCB at the source of the circuit. - again, fine, spare way available in the CU
  • Double pole residual current protection at 30mA AC to protect against electric shock from direct contact - covered by the Type A RCBO in the above linked socket
  • Protection against DC direct contact and prevention of potential blinding of type AC RCDs elsewhere in the installation. Can be incorporated into the AC residual protection by using a type B device or provided within a permanently connected EVSE - covered by the Mennekes granny charger itself
  • If you have a TN-C-S (also known as PME) supply, you need a method of protection against the shock risk from open PEN faults. There are 5 ways of doing this, each with their own disadvantages. The risk only exists outside so if you go down the protection device route rather than the earth rod route, it’s only necessary to protect the EVSE circuit. Using such a device to protect other circuits inside the house is unnecessary and would mean buying a higher rated and hence more expensive (and maybe non existent) devices
The last one is where I have the question - I do have a TN-C-S supply, so need the PEN fault protection. Is an earth rod alone going to satisfy this, or even with an earth rod would I need some sort of earth fault detection device too?

Additionally, second question would be what type of cable I'd need to run from the CU to the socket - as it's a 13amp socket (10amp continuous with the granny charger), I was thinking just 2.5mm2 T&E in conduit, but not sure if I need to go more chunky in terms of cabling here. Shouldn't think it has to be armoured either as it would run along the garage wall (internally).

Caveat: I am not a sparky, and wouldn't be touching the CU or anything else live without a professional here - I just like geeking out on it all and am happy to run cables and conduit etc. in advance of a proper sparky turning up.

guitarcarfanatic

1,596 posts

136 months

Saturday 6th April
quotequote all
ccr32 said:
This might be a question more appropriate for the EV section of the forum, but I am unsure what I need here from an electrical perspective.

I would like an EV compatible 3 pin plug on the front of the house (such as this: https://www.screwfix.com/p/masterplug-ip66-13a-1-g... - we only have a small capacity EV so don't really need a fast charger, but I'm reluctant to use the granny lead off one of our garage sockets long term as I don't know what the wiring is like upstream of that.

I understand that even for the above linked RCBO protected EV socket, I'd also need (as found in a post on another forum):
  • A specific final circuit for the charge point or socket - no problem, can run an independent cable to it from the CU which is in the garage
  • Over current protection for the cable and the equipment- normally a 32A MCB at the source of the circuit. - again, fine, spare way available in the CU
  • Double pole residual current protection at 30mA AC to protect against electric shock from direct contact - covered by the Type A RCBO in the above linked socket
  • Protection against DC direct contact and prevention of potential blinding of type AC RCDs elsewhere in the installation. Can be incorporated into the AC residual protection by using a type B device or provided within a permanently connected EVSE - covered by the Mennekes granny charger itself
  • If you have a TN-C-S (also known as PME) supply, you need a method of protection against the shock risk from open PEN faults. There are 5 ways of doing this, each with their own disadvantages. The risk only exists outside so if you go down the protection device route rather than the earth rod route, it’s only necessary to protect the EVSE circuit. Using such a device to protect other circuits inside the house is unnecessary and would mean buying a higher rated and hence more expensive (and maybe non existent) devices
The last one is where I have the question - I do have a TN-C-S supply, so need the PEN fault protection. Is an earth rod alone going to satisfy this, or even with an earth rod would I need some sort of earth fault detection device too?

Additionally, second question would be what type of cable I'd need to run from the CU to the socket - as it's a 13amp socket (10amp continuous with the granny charger), I was thinking just 2.5mm2 T&E in conduit, but not sure if I need to go more chunky in terms of cabling here. Shouldn't think it has to be armoured either as it would run along the garage wall (internally).

Caveat: I am not a sparky, and wouldn't be touching the CU or anything else live without a professional here - I just like geeking out on it all and am happy to run cables and conduit etc. in advance of a proper sparky turning up.
If running a dedicated circuit and using a 32amp breaker, you will need to chunk up to 4mm T+E. 2.5mm is only rated to about 24-26 amps when in radial form. If you change the breaker to 16amp, you can use 2.5mm (or even 1.5mm).

In terms of earth rod, use it’s fine if the resistance is low enough. Otherwise, you can get pen fault detection devices that work on PME.

Personally, the main issue with granny charges and normal sockets is heat as they are only designed for 10amp continuous / 13 amp peak. If it was me, I would just spur off the main ring and use an outside socket with the draw turned down to 10amp on the car (or an EV specific 13amp socket). As the EV charger is plug in equipment, regs wise, there is no issue. There is risk, but if going to the effort of a dedicated supply, just get a 7kwh charger off eBay and do a proper install. I think I paid £200 for my Easee charger…

Regbuser

3,510 posts

36 months

Saturday 6th April
quotequote all
..4mm T&E..

But we don't know:

Length of run
Fixing method
Any adverse conditions

So that may not be the correct cable

ruggedscotty

Original Poster:

5,627 posts

210 months

Saturday 6th April
quotequote all
Regbuser said:
..4mm T&E..

But we don't know:

Length of run
Fixing method
Any adverse conditions

So that may not be the correct cable
bingo.... peeps often forget that....

and cable needs to be right, no excessive volt drop - its stipulated in the requirements.

id go for a pme fault detector, dont want to depend on the one in the charger itself.

ammendment 2 allows install of a local earth rod and to connect that to your main earth terminal.

ccr32

1,981 posts

219 months

Saturday 6th April
quotequote all
Regbuser said:
..4mm T&E..

But we don't know:

Length of run
Fixing method
Any adverse conditions

So that may not be the correct cable
In my case, it would be under 10m run, and in the aforementioned conduit which would be fixed to the inside of the garage wall.

All that said, and given the earlier suggestion (seeing as my preference would still be to run a new cable from the CU), I’ve now started up looking up ‘proper’ 7kw chargers and going the whole hog instead.

Edited by ccr32 on Saturday 6th April 17:06

dhutch

14,390 posts

198 months

Sunday 7th April
quotequote all
ruggedscotty said:
I have a huge dislike for tester screwdrivers or non contact testers. Mains is dangerous, and it has the capacity to kill you. too many lulled into a false sense of security.
So what sort of tester do you use?

guitarcarfanatic

1,596 posts

136 months

Sunday 7th April
quotequote all
dhutch said:
So what sort of tester do you use?
What anyone playing with electric should be using - a proper voltage tester (and according to protocol, used in conjunction with a proving unit).

They start about £30, but if anyone wants a cheap basic one, I have a Klein ET45 which is well reviewed and only cost me about a tenner from Amazon. Works well and is tiny - I use it when I can’t be arsed to get the bigger one out biggrin

dhutch

14,390 posts

198 months

Sunday 7th April
quotequote all
Fair enough. And cheap enough.

Tony_T

742 posts

82 months

Wednesday 10th April
quotequote all
Why can't I sell these on ebay? Cost £250 plus vat and not a sniff at £30. Guessing they are just rarely used?



LED Emergency Light Conversion kits btw. P.s price is for 4.

AW10

4,439 posts

250 months

Wednesday 10th April
quotequote all
Normally fitted by a sparkie so not something bought by a DIYer? Unknown provenance so people not as willing to take the risk? What’s the shelf life of the batteries? That the installation date sticker goes from 2018 to 2024 suggests they have been sitting around for a while?

You really should list the part numbers so the listing gets found during a search. Leaving them out is just… lazy… and not helping you sell them.

Tony_T

742 posts

82 months

Wednesday 10th April
quotequote all
AW10 said:
Normally fitted by a sparkie so not something bought by a DIYer? Unknown provenance so people not as willing to take the risk? What’s the shelf life of the batteries? That the installation date sticker goes from 2018 to 2024 suggests they have been sitting around for a while?

You really should list the part numbers so the listing gets found during a search. Leaving them out is just… lazy… and not helping you sell them.
Cheers, have now added the part number to the title and description.

Gary C

12,471 posts

180 months

Thursday 11th April
quotequote all
guitarcarfanatic said:
dhutch said:
So what sort of tester do you use?
What anyone playing with electric should be using - a proper voltage tester (and according to protocol, used in conjunction with a proving unit).

They start about £30, but if anyone wants a cheap basic one, I have a Klein ET45 which is well reviewed and only cost me about a tenner from Amazon. Works well and is tiny - I use it when I can’t be arsed to get the bigger one out biggrin
Martindale is the only tester approved for use where I work (well, on up to 415V after that we use Metrohm HV test sticks). Both come with proving units.

But the key for ultimate safety is test the tester, test the circuit, test the tester and any voltmeter can do that.

But I bet very few of us do it at home smile

Mogsmex

448 posts

236 months

Thursday 11th April
quotequote all
after some knowledge here on what my options are.........

I wish to fit a couple of outside lights in my garden, I wish to control them from a spare switch already in the wall by the back door

I have power in the shed(s) at the bottom of the garden but nothing else, I dont wish to dig up the patio or run any wiring down the garden if possible, failry sure there is a wiring in place under/at the side of the patio from said switch that could be directed to water proof box etc

is there a wifi/radio signal relay device I can use ?

at the moment it appears a wifi plug in the shed and just usiing an app is the front runner but would like to use the switch by the back door if possible

Thanking you smile

Regbuser

3,510 posts

36 months

Thursday 11th April
quotequote all
Something like this would work



But you'll need a neutral in the back box of the switch.

dhutch

14,390 posts

198 months

Thursday 11th April
quotequote all
AW10 said:
Normally fitted by a sparkie so not something bought by a DIYer? Unknown provenance so people not as willing to take the risk? What’s the shelf life of the batteries? That the installation date sticker goes from 2018 to 2024 suggests they have been sitting around for a while?
Also most DIYers are going to be adding maybe one or two, not four?

Steve Campbell

2,136 posts

169 months

Friday 12th April
quotequote all
Steve Campbell said:
Is there a simple way to find out why no power is being fed to a light ?

Here's the problem > When we moved in 17 years ago, I had a large drinks cabinet for the dining room. Dining room had 3 uplighters. I removed the uplighter and made safe the wires on one of them where I wanted to put the cabinet against the wall. No idea if it was working at the time as this was on the day of moving in.

17 years later, the cabinet has gone and new uplighters now fitted....but the one that was blanked off doesn't work !

I have an electrician coming around next week anyway but was just wondering. Electrician also going to fix my idiot mistake of replacing other lights and not checking what wires connected to what before disconnecting the light.....so I have 4 wires coming in consisting of 4 reds, 3 blacks, one blue and 2 earths !.......and have no idea which one is the switch etc etc ! Just so happens the first one I took apart is the primary link to all the others (4 other lights and 2 other rooms !). Oh well........
All's well that ends well. The electrician had an easy job and probably had a chuckle at my ineptitude with the lights. He got his call out fee and had it all sorted in 20 mins. Quickly figured out the old pendant light wiring and got it sorted. The non-working light ? Whoever had the house before us had disconnected that light in one of the 2 switches and just taped it off ! No idea why. Anyway, always check the switch first :-). I wouldn't have known which wire to put where. At least I knew when to call in a professional !

miniman

24,976 posts

263 months

Friday 12th April
quotequote all
What would an appropriate way to power this be?


essayer

9,077 posts

195 months

Friday 12th April
quotequote all
Fused spur or worst case a plug with a nice low fuse
Put it in an enclosure (the screws are live!) and ensure the supply cable is secured inside and out so it can’t be pulled out

cogflation

12 posts

1 month

Friday 12th April
quotequote all
Actual said:
FLUKE AC NON-CONTACT VOLTAGE DETECTOR PEN 1000V AC
.screwfix.com/p/fluke-ac-non-contact-voltage-detector-pen-1000v-ac/85949

Unlike other pen type detectors this one is more safe to use and will glow red when you position it next a live wire.

Just so you know it is working it is advisable to make sure it is turned on and check a known live wire before and after checking the wire being tested.

Edited by Actual on Thursday 4th April 11:34
More safe?scratchchin

Safe doesn't belong in the sentence. Comparing glow sticks and neon screwdrivers on safety grounds is akin to comparing stringfellow and Andrew Tate as to who is a more appropriate first date for your daughter.