Is my central heating timer goosed?

Is my central heating timer goosed?

Author
Discussion

blueST

Original Poster:

4,394 posts

216 months

Friday 1st February 2013
quotequote all
We've got a normal gas central heating system with a Honeywell timer programmer the same as this http://www.honeywelluk.com/products/Time-Controls/...

I think it may be faulty, but maybe someone can advise. The heating comes on an off with the set programme as it should, i.e. on in the morning, off during the day and on again at night.

The problems start if you try to override the programme, by pressing the button to the right of the slider switch. This should turn the heating on if it's currently off, or turn it off if it's currently on. If I want the heating on and I press the button, the light comes on to show it's has activated and I can (sometimes) here the zone valves motoring about, but the boiler doesn't fire up and the pump doesn't activate.

I've tried a hard reset, still no joy.

Would you say this is likely to be the programmer? If it is, I'll just swap it like for like. Or do I need someone to look into it more deeply?

silversurfer1

919 posts

136 months

Friday 1st February 2013
quotequote all

It does sound like its is the programmer if it only happens whilst using the advance button. The only was to be sure would be to check the electrical signal at the valve or valves when the fault has arisen.

You would be looking for a 240vac signal at the white cable (heating on) if its a "Y" plan, or brown cable at the associated zone valve if its an "S" plan.

regards

j


Deva Link

26,934 posts

245 months

Friday 1st February 2013
quotequote all
Do you hear the relay in the timer click when you press the button?

It's a bit of an odd fault, especially if the indicator on the timer goes on and off as you'd expect, and the system works as expected when left to its own devices.

When you turn it on by using the advance button, is there definitely a call for heat (ie actual temp is below thermostat setting)?

blueST

Original Poster:

4,394 posts

216 months

Friday 1st February 2013
quotequote all
The thermostat is set to 22 and the room temp was showing as about 16. So it should be firing up.

I can here a relay click when I press the button. Sometimes I hear a zone valve move too. Strange.

blueST

Original Poster:

4,394 posts

216 months

Friday 1st February 2013
quotequote all
Double post, ignore.

Rickyy

6,618 posts

219 months

Friday 1st February 2013
quotequote all
You need to test voltages really, but those timers are quite prone to dying. They still make them, so you can do a direct swap.

blueST

Original Poster:

4,394 posts

216 months

Monday 11th February 2013
quotequote all
I did a direct swap of the programmer, like for like, over the weekend, and I've still got the same problem. Time to stop clutching at straws, hit Rated People and get a man in.

blueST

Original Poster:

4,394 posts

216 months

Saturday 16th February 2013
quotequote all
Turns out it was one of the zone valves. It would function fine most of the time, but every now and again it wouldn't move through it's whole travel, and so not hit the contacter to trigger the boiler. I guess it must have also stuck fully open at some point, explaining why we couldn't turn the heating off on one occasion.

spants

1,053 posts

227 months

Sunday 17th February 2013
quotequote all
Had the same problem with the same remedy. Bought new synchro motor from screwfix for about a tenner. Sorry I didn't see this earlier to help you.

My motor had heated up so much that the insulation on the wires going to the motor had disintegrated.......