Finished floor level same as ground level

Finished floor level same as ground level

Author
Discussion

pattieG

Original Poster:

196 posts

150 months

Wednesday 7th February 2018
quotequote all
Hello.

I am designing my extension and I have come up against a problem. It appears my FFL is the same as ground level outside. Incidentally I've also noticed that on the plans for other houses built at the same time on my road that they show the FFL as 150mm above ground level. I know this is a requirement for current building regulations but I don't see how this will work unless I put a step from the existing house into the extension.

Is there a workaround for this or are my measurements wrong?

Equus

16,980 posts

102 months

Wednesday 7th February 2018
quotequote all
It is a requirement that the DPC is at least 150mm above ground level... the floor can be wherever you want it (obviously even well below ground level, in the case of basements) so long as it is there is a suitable DPM, linked to the DPC (and if below ground, that DPM will need to be able to resist hydrostatic pressure... tanking. in other words). Refer to the NHBC 'Standards' for further guidance.

But the obvious question is: if the mountain won't come to Mohammad... can you not simply lower the external ground level?


pattieG

Original Poster:

196 posts

150 months

Wednesday 7th February 2018
quotequote all
Would the 1200g membrane for the concrete floor be placed up the inside wall leaf and then lapped over the DPC in the wall?

Edited by pattieG on Wednesday 7th February 13:15

Equus

16,980 posts

102 months

Wednesday 7th February 2018
quotequote all
It depends on the ground level difference; if the external ground is the same or a little lower than the SFL, then most BCO's will accept that, yes. If not, then refer to the NHBC Standards (section 5.4).

pattieG

Original Poster:

196 posts

150 months

Wednesday 7th February 2018
quotequote all


Magenta line is the Membrane going up the wall and lapped with the DPC three courses above ground level.

Or if BCO don't like that then a type A waterproofing barrier.


Edited by pattieG on Wednesday 7th February 13:54

barryrs

4,398 posts

224 months

Wednesday 7th February 2018
quotequote all
This is the detail I generally use for a raised ground level.


Equus

16,980 posts

102 months

Wednesday 7th February 2018
quotequote all
^^^ Yes, that sort of detail: DPM lapped up the cavity face of the inner leaf is better.

It would be prone to damage if on the inner (exposed) face of the inner leaf, as you'd shown (and also means that your plaster wouldn't bond to the wall if you're wet plastering... though of course most people dry line these days, in which case the dry lining protects the DPM better and most BCO's would tolerate the detail as you'd drawn it, albeit it's not ideal).

magooagain

10,053 posts

171 months

Wednesday 7th February 2018
quotequote all
Attention to the skirting installation. Probably stuck onto the plaster finish.