Ariston Boiler E 02 code, loss of pressure

Ariston Boiler E 02 code, loss of pressure

Author
Discussion

z4chris99

Original Poster:

11,290 posts

179 months

Thursday 27th September 2012
quotequote all
my fking boiler is playing up.. its fine heating water, but when it comes to the rads it throws up E 02, which i read is loss of pressure.. no problem i thought ill just pump more water into the system..

but

whichever combination of the two taps from the water in and the rad system i cannot get the pressure valve to move.

any ideas?


z4chris99

Original Poster:

11,290 posts

179 months

Thursday 27th September 2012
quotequote all



z4chris99

Original Poster:

11,290 posts

179 months

Thursday 27th September 2012
quotequote all
Rickyy said:
Turn them both parallel with the valve bodies and play about with the braided hose, they usually kink and restrict the flow of water.
nada no worky...

maybe ill replace the hose tomorrow.. there is water coming out the right side as if you turn the little thingy it sprays out..

its on half a bar... on the edge of red and blue..

z4chris99

Original Poster:

11,290 posts

179 months

Thursday 27th September 2012
quotequote all
Gingerbread Man said:
Bootiful install that.
dodgey 1985 developers...

z4chris99

Original Poster:

11,290 posts

179 months

Thursday 27th September 2012
quotequote all
just replaced the left valve.. i had a random spare in a drawer.. the old one was fked and not opening.

works fine now. job done...

z4chris99

Original Poster:

11,290 posts

179 months

Friday 28th September 2012
quotequote all
fourpointsixgt said:
z4chris99 said:
Gingerbread Man said:
Bootiful install that.
dodgey 1985 developers...
1985?? condensing combi, more like 2005 or later.
would be news to me, maybe the dodgey estate agents who used to manage it for me put it in,